8-1 Inspection and Maintenance
Daily Inspection and Periodic Inspection
Inspection
part
General Ambient
Main
circuit
8
8-3
Inspection
Inspection point
item
Check ambient
environment
temperature, as
well as humidity
and dust levels.
Entire
Check that there are
device
no abnormal
vibrations or sounds.
Power
Check that the
supply
main circuit
voltage
voltage is normal.
General
Megger check
(between main
circuit terminal
and ground
terminal)
Check that any
parts which may
need tightening
are secure.
Check that no
part has
indications of
overheating.
Inspection
period
Periodic
Inspection
method
Refer to
"Installation" on
page 2-1.
√
Visual or acoustic
√
inspection
Measure the
voltage between
√
the Inverter main
circuit terminals R/
L1, S/L2 and T/L3.
Remove the I/O
wirings of the
Inverter's main
circuit terminal
block, remove the
control terminal
block board, and
remove the
Inverter's built-in
filter function
√
switching shorting
bar, and then use
a megger to
measure between
the shorted part of
each terminal R/
L1, S/L2, T/L3, U/
T1, V/T2, W/T3,
P/+2, +1, N/− or
RB and the
ground terminal.
Tighten securely.
√
Visual inspection
√
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
Measurement
Criteria
device
The ambient
Thermometer
temperature shall
Hygrometer
be −10 to 50 °C,
Recorder
non-freezing, and
the ambient
humidity shall be
90% or below,
non-condensing.
No faults
Must be within
Tester,
allowable
digital
fluctuation of AC
multimeter
voltage.
5 MΩ min.
500 V
class DC
megger
No faults
No faults