Example of Basic Operations
An example of basic parameter change operations is given below.
<Operation example of changing RUN Command Selection (A002) from Digital
Operator (02) to Terminal Block (01) when "0.00" is shown on the output frequency
monitor screen after the power has been turned ON>
Output Frequency
Monitor
(5) Press the Increment key to
increment the parameter by 1.
RUN Command Selection
(9) Pressing and holding the Enter key
(for 1 second or more) jumps to the
output frequency monitor display.
Since F parameters other than F004 are reflected in real time the moment they are changed,
the display does not blink when any of these parameters is changed.
Key arrangement
Mode key
Enter key
Increment key
Decrement key
Increment/Decrement are
pressed simultaneously
Reference
Regardless of the Digital Operator display, pressing and holding the Mode key (for 1 second or
more) displays the data for Output Frequency Monitor (d001) again. However, the selected mode
continues to cycle among the function groups while the Mode Key is held, according to the
designed operation of the key. (Example: A001→F001→b001→C001→...Elapse of 3 seconds,
followed by display of "50.00")
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
(2) Press the Mode Key to
display the parameters.
dk0k0k1
(3) Press the Mode Key to move the function group.
fk0k0k1
(4) Press the Mode Key to move the function group.
ak0k0k1
(6) Press the Enter key to
move to the data display.
ak0k0k2
(8) Press the Enter key to
confirm and store the value.
Key name
Function code is displayed
Move to the next function group Value is cancelled and
Proceed to the data display
Parameter is incremented by 1 Data is incremented by 1
Parameter is decremented by 1 Data is decremented by 1
Move to the individual input
mode
3-1 Name of Parts of the Digital Operator
(1) The d001 (Output Frequency Monitor)
data is displayed during power ON time.
(Default setting)
0.0k0
When the display first appears,
0k2
all data digits are lit.
(7) Press the Decrement key to
decrement the data by 1.
If data is changed, all digits will blink.
0k1
The new data is not yet reflected
while its digits are still blinking.
return to the parameter display
Value is confirmed/stored and
return to the parameter display
Move to the individual input
mode
Data is displayed