Pulse Train Frequency Input

This function uses the pulse train (1 phase) input to the RP terminal, as the frequency
reference or PID feedback value in each control mode.
Set the input frequency at the maximum frequency in Pulse Train Frequency Scale (P055).
The analog input start/end function cannot be used. To limit the input frequency, use Pulse
Train Bias Amount (P057) and Pulse Train Limit (P058).
Parameter
No.
P003
P055
P056
P057
P058
A001
A076
A141
A142
Frequency
measurement
Frequency Scale (P055)
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
Function name
Pulse Train Input Terminal
RP Selection
Pulse Train Frequency
Scale
Pulse Train Frequency
Filter Time Parameter
Pulse Train Bias Amount
Pulse Train Limit
Frequency Reference
Selection
PID Feedback Selection
Operation Frequency
Selection 1
Operation Frequency
Selection 2
%
1
Hz
1 + sT
(1.0 to 32 kHz)
Primary Delay Filter (P056)
5-6 Operation Functions
Data
00: Frequency setting or PID
feedback value
1.0 to 32.0
Specify the input pulse frequency at
the motor's Maximum Frequency
(A004).
0.01 to 2.00
Set the filter time constant for pulse
train input.
−100. to +100.
0. to 100.
06: Pulse train frequency
03: Pulse train frequency
07: Pulse train frequency
Bias limit
Limit
%
Bias
Maximum Frequency
(A004)
Default
Unit
setting
00
25.0
kHz
0.10
s
0.
%
100.
%
02
00
02
03
Hz
Frequency
Reference
5-82
5