Omron SYSDRIVE MX2 SERIES User Manual page 85

Multi-function compact inverter
Hide thumbs Also See for SYSDRIVE MX2 SERIES:
Table of Contents

Advertisement

Parameter No. Function name
Overload Limit 1
b026
Parameter 2
Overcurrent
b027
Suppression
Selection
Frequency Pull-
b028
in Restart Level
Frequency Pull-
b029
in Restart
Parameter
Starting
Frequency at
b030
Frequency Pull-
in Restart
Selection
Soft Lock
b031
Selection
Motor Cable
b033
Length Code
Selection
RUN Time/Power
b034
ON Time Level
Rotation
b035
Direction Limit
Selection
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-Axxxx)
Monitor or data range
0.1 to 999.9
1000. to 3000.
00: Disabled
01: Enabled
0.20 × Rated current to 2.00 ×
rated current (heavy load
setting)
0.20 × Rated current to 1.50 ×
rated current (light load
setting)
0.1 to 999.9
1000. to 3000.
00: Frequency at interruption
01: Maximum frequency
02: Set frequency
00: Data other than b031
cannot be changed when
terminal SFT is ON.
01: Data other than b031 and
set frequency cannot be
changed when terminal
SFT is ON.
02: Data other than b031
cannot be changed.
03: Data other than b031 and
set frequency cannot be
changed.
10: Data can be changed
during RUN.
5. to 20.
0. to 9999. (0 to 99990)
1000 to 6553 (100000 to
655350)
00: No direction limit
01: Only Forward is enabled
(Reverse is limited)
02: Only Reverse is enabled
(Forward is limited)
4-2 Function Mode
Data can
Data can be
Default
be set
Set data
changed
setting
during
during RUN
RUN
1.0
no
yes
00
no
yes
Inverter
rated
no
yes
current
0.50
no
yes
00
no
yes
01
no
yes
10.
no
yes
0.
no
yes
00
no
no
Unit Page
s
5-114
5-116
A
5-97
5-100
s
5-103
4
5-84
5-145
h
5-124
5-23
4-18