The following Check Off Lists must be completed prior to final operation of the
Fireplace, or manufacturer's warranty and liabilities will be voided:

INSTALLATION CHECK OFF LIST

Co-axial vent rigid pipe, wall vent cap or roof vent cap must be installed by a
Mendota approved person in accordance with instructions. All joints must be se-
cured, "twist-locked" and leak-proof. 2000
sealant must be used on the inner
º
pipe joints of all adjustable pipe sections (Dura Vent only).
Horizontal or vertical vent cap must be installed "right-side-up" and tightly
sealed to structure per instructions. Vent Caps must be Mendota approved.
Proper exterior and interior clearances for vent systems and locations for wall
vent cap/roof vent cap must be maintained (See PAGEs 8-18.)
Carefully check for correct gas pressure, proper size gas lines (see PAGEs. 6 & 7)
and for gas leaks.
120 V electrical service and gas supply must be installed in accordance with in-
structions and local and national codes.

LIGHTING CHECK OFF LIST

All items on "Installation Check Off List" (see above) must be completed.
Connect thermostat to gas valve's TH and THTP terminals. See PAGE 37.
Perform Leak Test on ALL gas fittings on gas train using soap-water solution or
a calibrated combustible gas detector.
System millivolt readings (see PAGE 37) must be taken by a qualified installer.
CAUTION: Pilot flame must register a minimum of 250 millivolts.
Check air shutter opening - 1/8" to 1/4" Nat. gas or 1" LP gas (see PAGE 35).
Carefully follow all Lighting and Log Installation Instructions.
Make certain that burner lights immediately and flame runs promptly around
"curve" in burner and lights entire burner. DO NOT proceed with operation un-
less burner cycles "on/off" without delays.
Make certain that the flame is "stable" and does not "lift" off burner. If flame lifts
off burner, turn unit off and check that vent pipes are twist-locked and leak proof
and vent cap is "right side up".
DO NOT proceed with operation if flame is "lifting off" burner.
Make certain glass door is in properly closed position and "centered" in firebox
opening (see PAGE 22).