Table 7. Environmental and Safety
Operating Temperature
Transit/Storage
Temperature
Relative Humidity
Operating Altitude
Audible Noise
Surge Suppression
Safety Conformance
Safety Markings
EMC (Class B)
Table 8. Battery
UPS Configuration
Voltage
Type
Charging
Monitoring
Eaton 5115 Tower UPS (500–1400 VA) User's Guide
120V Models
Up to 1,500 meters: 0°C to 40°C (32°F to 104°F); UL tested 25°C (77°F)
Above 1,500 meters: 0°C to 35°C (32°F to 95°F)
Up to 3,000 meters above sea level
ANSI C62.41 Category A (formerly IEEE 587)
UL 1778 2nd Edition; UL 497A;
CSA C22.2, No. 107.1
cULcs, cUL
FCC Part 15, ICES-003
500 VA: (1) 12V, 9 Ah internal battery
750 VA: (2) 12V, 7 or 7.2 Ah internal batteries
1000 VA: (2) 12V, 9 Ah internal batteries
1400 VA: (3) 12V, 9 Ah internal batteries
Sealed, maintenance‐free, valve‐regulated, lead‐acid
Advanced charging for faster recovery; approximately 3 hours to 90% usable capacity at
nominal line and no supplementary power supply load
Advanced monitoring for earlier failure detection and warning
-15°C to 55°C (5°F to 131°F)
5–95% noncondensing
Less than 45 dBA typical
UL 1778 2nd Edition, UL 497A
IEC/EN 62040-1-1 and IEC/EN 60950
cULcs, cUL, CE, TÜV, C-Tick
IEC/EN 62040-2, FCC Part 15, ICES-003
500 VA: 12 Vdc
750–1000 VA: 24 Vdc
1400 VA: 36 Vdc
S
05146640 Rev D www.eaton.com/powerquality
SPECIFICATIONS
230V Models
(data line only);
CSA C22.2, No. 107.1;
49