A13)
In a Master/Slave network the multiplexed hot gas defrost is always
synchronized by the Master. The safety procedure switches the Slave OFF
if it is offl ine (no longer by the Master across the tLAN).
Par.
Description
A13
Hot gas safety procedure for Slave offl ine
0 = not enabled; 1 = enabled
Alarm log (parameters HS0 to HS9)
The alarm log can be displayed by accessing parameters HS0 to HS9,
rather than using the procedure described in paragraph 9.3.
Par.
Description
HS0 to 9 Alarm 0 to 9 (press Set)
---
Alarm 0 to 9 - Code
h__
Alarm 0 to 9 - Hours
n__
Alarm 0 to 9 – Minutes
---
Alarm 0 to 9 - Duration
9.6 HACCP alarm parameters and activating
monitoring
Type HA alarms
The alarm queue can be displayed by accessing parameters HA to HA2,
rather than using the procedure described in paragraph 9.4. The type
HA alarm is generated if during normal operation the temperature
read by the probe set for parameter AA exceeds the high temperature
threshold for the time Ad+Htd. Consequently, compared to the normal
high temperature alarm already signalled by the controller, the type HA
HACCP alarm is delayed by a further time Htd specifi cally for HACCP
recording. The order of alarms listed is progressive, HA is the most recent
alarm. A maximum of 3 errors are saved, in a FIFO list (HA to HA2). HAn
indicates the number of type HA alarms activated.
Par.
Description
Ht0
HACCP alarms present
HAn
Number of type HA alarms
HA to
Type HA HACCP alarms activated (press
HA2
Set)
y__
Alarm 1 to 3 - Year
M__
Alarm 1 to 3 - Month
d__
Alarm 1 to 3 – Day of the month
h__
Alarm 1 to 3 – Hour
n__
Alarm 1 to 3 – Minutes
---
Alarm 1 to 3 – Duration
Htd
HACCP alarm delay
0 = monitoring disabled
AH
S
St
ON
ALARM
OFF
MPXPRO - + 0300055EN rel. 1.0 30/08/10
Def
Min
Max
0
0
1
Tab. 9.g
Def
Min
Max
-
-
-
-
-
-
0
0
23
0
0
59
0
0
999
Tab. 9.h
Def
Min
Max
UoM
0
0
1
0
0
15
-
-
-
0
0
99
0
1
12
month
0
1
31
0
0
23
hour
0
0
59
minute
0
0
240 minute
0
0
240
Tab. 9.i
t
t
Ad Htd
Fig. 9.c
Key
S
Measurement probe
St
Set point
High temperature alarm
AH
threshold
UoM
ALARM
Type HA HACCP alarm
-
Type HF alarms
The type HF HACCP alarm is generated following a power failure for an
extended time (> 1 minute), if when power returns the temperature
read by probe set for parameter AA exceeds the AH high temperature
threshold. HFn indicates the number of type HF alarms activated.
Par.
Description
UoM
HFn
Number of type HF alarms
-
HF to HF2 Type HF HACCP alarms activated
-
(press Set)
hour
min
y__
Alarm 1 to 3 - Year
M__
Alarm 1 to 3 - Month
min
d__
Alarm 1 to 3 – Day of the month
h__
Alarm 1 to 3 – Hours
n__
Alarm 1 to 3 – Minutes
---
Alarm 1 to 3 – Duration
S
ALARM
Key
S
Measurement probe
St
Set point
High temperature alarm
AH
threshold
-
-
-
year
day
66
Delay time for high and low
Ad
temperature alarms
HACCP alarm delay
Htd
0 = monitoring disabled
t
Time
Def
Min
0
-
0
0
0
0
0
0
AH
St
ON
OFF
black out
Fig. 9.d
ALARM
Type HF HACCP alarm
t
Time
Max
UoM
0
15
-
-
-
-
0
99
year
1
12
month
1
31
day
0
23
hour
0
59
minute
0
240
minute
Tab. 9.j