Carel MPXPRO User Manual page 61

Electronic controller
Hide thumbs Also See for MPXPRO:
Table of Contents

Advertisement

Par.
Description
P12
LSA: alarm delay
0 = alarm disabled
P13
LSA: alarm diff erential (°C)
0 = reset always automatic
P14
Enable valve alarm at end travel ('blo')
1 = signal enabled
P15
Support saturated temperature for pressure probe error
PH
Type of refrigerant
1 = R22
2 = R134a
3 = R404A
4 = R407C
5 = R410A
6 = R507A
7 = R290
OSH
Superheat off set for modulating thermostat
0 = function disabled
Phr
Enable fast update of the valve parameters to supervisor
0 = fast update disabled
PM1
MOP: maximum saturated evaporation temperature threshold
PM2
MOP: integration time
PM3
MOP: alarm delay
0 = function disabled
PM4
MOP: delay activation of function when starting control
PM5
MOP: enable close solenoid valve
0 = closing disabled; 1 = closing enabled
PL1
LOP: minimum saturated evaporation temperature threshold
PL2
LOP: integration time
PL3
LOP: alarm delay
0 = function disabled
SH
Superheat
PPU
Valve opening percentage
tGS
Superheated gas temperature
tEu
Saturated evaporation temperature
/cE
Saturated evaporation temperature calibration
Po6
PWM expansion valve Ton + Toff period
cP1
Initial valve position when control starts
Pdd
Initial valve position maintenance time after defrost
PSb
Valve standby position
PF
Valve opening steps (supervisor)
PMP
Enable manual expansion valve positioning
0 = disabled; 1 = enabled
PMu
Manual valve position
Phc
Enable high current valve driving
CnF (Confi guration)
In
Type of unit
0 = Slave;1 = Master
Sn
Number of slaves in the local network
0 = no Slave
H0
Serial or Master Slave network address
H1
Confi gure function of output AUX1
0 = No function
1 = Normally de-energized alarm
2 = Normally energized alarm
3 = Auxiliary
4 = Auxiliary serving MASTER on the Slaves
5 = Light
6 = Light serving the Master on the Slaves
H2
Disable keypad and remote control functions
1 = keypad and remote control enabled
H3
Remote control enabling code
0 = programming from remote control without code
H4
Terminal buzzer (if present)
0 = enabled; 1= disabled
H5
Confi gure function of output AUX2 see H1
H6
Terminal keypad lock confi guration
H7
Confi gure function of output AUX3 see H1
H8
Output switched with time bands
0 = Light; 1 = AUX
H9
Select function associated with the "aux" button on the user terminal
0 = Light; 1 = AUX.
H10
Confi gure compressor digital output logic
0 = direct logic; 1 = reverse logic
H11
Confi gure evaporator fan digital output logic
0 = direct logic; 1 = reverse logic
H12
Light sensor threshold
H13
Confi gure function of output AUX4 see H1
8 = R600
9 = R600a
10 = R717
11 = R744
12 = R728
13 = R1270
14 = R417A
7 = Auxiliary evaporator defrost
8 = Evaporator fans
9 = Anti-sweat heaters
10 = Suction valve
11 = Equalizing valve.
12 = Solenoid valve.
61
Pag.
Def
Min
Max
UoM
55
600
0
999
s
55
10.0
0.0
60.0
°C/°F
67
1
0
1
-
53
-15.0
-50.0
50.0
°C/°F
28-51
3
1
14
-
53
0.0
0.0
60.0
K
52
0
0
1
-
54
50.0
-50.0
50.0
°C/°F
54
10.0
0.0
240.0
s
54
0
0
999
s
54
2
0
240
s
54
0
0
1
-
55
-50.0
-50.0
50.0
°C/°F
55
0.0
0.0
240.0
s
55
0
0
240
s
40-56
-
-
-
K
40-56
-
-
-
%
40-56
-
-
-
°C/°F
40-56
-
-
-
°C/°F
41
0.0
-20.0
20.0
°C/°F
56
6
1
20
s
52
30
0
100
%
52
10
0
30
min
52
0
0
400
step
56
-
0
-
step
56
0
0
1
-
56
-
0
600
step
56
0
0
1
-
28
0
0
1
-
28
0
0
5
-
28
199
0
199
-
33
8
0
12
-
57
1
0
5
-
33
0
0
255
-
57
0
0
1
-
33
2
0
12
-
57
0
0
15
-
33
5
0
12
-
33
0
0
1
-
33
0
0
1
-
44
0
0
1
-
44
0
0
1
-
42
25
10
100
lux
33
12
0
12
-
MPXPRO - + 0300055EN rel. 1.1 30/08/10
ENG
Type
Icon
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
F
F
F
F
A
A
A
A
A
NV
A
A
A
C
C
C
C
A
A
A
C
A
C
C
C
A
A
A
C