Table Of Alarms; Alarm Parameters - Carel ir33 Universale series User Manual

Universale electronic controller
Hide thumbs Also See for ir33 Universale series:
Table of Contents

Advertisement

ENG

8.4 Table of alarms

Message
Cause of the alarm
on display
E01
Probe B1 fault
E02
Probe B2 fault
E03
Digital contact open
(immediate alarm)
E04
The temperature measured
by the probe has exceeded
the threshold P26 for a time
greater than P28.
E05
The temperature measured
by the probe has fallen
below threshold P25 for a
time greater than P28.
E03
Digital contact open
(delayed alarm)
E03
Digital contact open
(immediate alarm with
manual reset)
E06
Real time clock fault
E07
EEPROM error, unit
parameters
E08
EEPROM error, operating
parameters
E09
Acquisition error.
Reached max. time in
calculation of PID parameters.
E10
Calculation error:
PID gain null.
E11
Calculation error:
PID gain negative
E12
Calculation error:
Integral & deriv. time negative
E13
Acquisition error.
Reached max. continuous time
in calculation of gain.
E14
Error when starting.
Situation not suitable
The alarms that occur during the Auto-Tuning procedure are not put in
the alarm queue.

8.5 Alarm parameters

The following parameters determine the behaviour of the outputs when
an alarm is active.
8.5.1 Status of the control outputs with probe alarm
(parameter c10)
This determines the action on the control outputs when there is a control
probe alarm E01, which may be one of the four responses envisaged.
When OFF is selected, the controller shuts down immediately and the
timers are ignored. When ON is selected, on the other hand, the "Delay
between activations of two diff erent relay outputs" (parameter c6) is
observed. When alarm E01 is resolved, the controller restarts normally
and the alarm output, if set, terminates the signal (see mode 5). On the
other hand, both the signal on display and the buzzer remain active until
Prg/mute is pressed.
ir33 universale +030220801 - rel. 1.0 - 16.04.2008
Icon on display Alarm relay
Buzzer Reset
OFF
fl ashing
OFF
fl ashing
ON
fl ashing
ON
fl ashing
ON
fl ashing
ON
fl ashing
ON
The alarm relay
fl ashing
is activated
according to the
OFF
operating mode
fl ashing
and/or the
dependence
OFF
fl ashing
OFF
fl ashing
ON
fl ashing
ON
fl ashing
ON
fl ashing
ON
fl ashing
ON
fl ashing
ON
fl ashing
Code
Control action
shown in
alarm queue
ALx_TYPE
automatic
E01
Depends on
parameter c10
automatic
E02
If c19=1 & c0=1/2,
as for E01, otherwise
control does not
stop.
automatic
E03
Based on parameter
c31
automatic
E04
No eff ect on control Check parameters P26,P27,
automatic
E05
No eff ect on control Check parameters P25,P27,
manual
E03
Based on parameter
c31
manual
E03
Based on parameter
c31
automatic
-
-
/manual
automatic
-
Total shutdown
automatic
-
Total shutdown
manual
-
Auto-Tuning
stopped
manual
-
Auto-Tuning
stopped
manual
-
Auto-Tuning
stopped
manual
-
Auto-Tuning
stopped
manual
-
Auto-Tuning
stopped
manual
-
Auto-Tuning
stopped
42
Checks/solutions
Check probe connections
Check probe connections
Check parameters
c29,c30,c31.
Check the external contact.
P28,P29
P28,P29
Check parameters c29,c30,
c31,P28.
Check the external contact.
Check parameters
c29,c30,c31. Check the
external contact.
Reset the clock time.
If the alarm persists,
contact service.
Contact service
Reset default values using
the procedure described. If
the alarm persists, contact
service.
Reset the alarm manually
or switch the controller off
and on again