Table Of Parameters - Carel MPXPRO User Manual

Electronic controller
Hide thumbs Also See for MPXPRO:
Table of Contents

Advertisement

Parameter levels: F = frequent, C=confi guration (password=22),
A=advanced (password=33)
Par.
Description
/Pro (=PROBES)
/2
Analogue probe measurement stability
/4
Virtual probe composition
0 = Outlet probe Sm
100 = Intake probe Sr
/5
Temperature unit of measure
0 =°C, 1=°F
/6
Display decimal point
0 = Enabled, 1 = Disabled
rHS
Virtual probe composition for glass temperature probe estimate
0 = Outlet probe Sm
100 = Intake probe Sr
/t
Display signals / alarms on remote display
0 = Disabled, 1 = Enabled
/t1
Display on user terminal
0 = User terminal disabled
1 = Probe 1
2 = Probe 2
3 = Probe 3
4 = Probe 4
5 = Probe 5
6 = Probe 6
7 = Probe 7
/t2
Display on remote display
0 = Remote display disabled
1 = Probe 1
2 = Probe 2
3 = Probe 3
4 = Probe 4
5 = Probe 5
6 = Probe 6
7 = Probe 7
/to
Confi gure user terminal/remote display
User terminal
0
Present
1
Optional
2
Present
3
Optional
/P1
Type of probe, group 1 (S1, S2, S3)
0 = NTC Standard Range –50T90°C
1 = PTC Standard Range –50T150 °C
2 = PT1000 Standard Range –50T150 °C
3 = NTC L243 Standard Range –50T90 °C
/P2
Type of probe, group 2 (S4, S5)
0 = NTC Standard Range –50T90 °C
1 = PTC Standard Range –50T150 °C
2 = PT1000 Standard Range –50T150 °C
3 = NTC L243 Standard Range –50T90 °C
/P3
Type of probe, group 3 (S6)
0 = NTC Standard Range –50T90 °C
1 = PTC Standard Range –50T150 °C
2 = PT1000 Standard Range –50T150 °C
3 = NTC L243 Standard Range –50T90 °C
4 = 0 to 5V ratiometric probe
/P4
Type of probe, group 4 (S7)
0 = NTC Standard Range –50T90 °C
1 = PTC Standard Range –50150 °C
2 = PT1000 Standard Range –50T150 °C
3 = NTC L243 Standard Range –50T90 °C
4 = 0 to 5V ratiometric probe
5 = 0 to 10 V input
6 = 4 to 20 mA input
/P5
Type of probe, group 5: serial probes (S8 to S11)
/FA
Assign outlet temperature probe (Sm)
0 = Function disabled
1 = Probe S1
2 = Probe S2
3 = Probe S3
4 = Probe S4
5 = Probe S5
/Fb
Assign defrost temperature probe (Sd) - See /FA
/Fc
Assign intake temperature probe (Sr) - See /FA
/Fd
Assign superheated gas temperature probe (tGS) - See /FA
/FE
Assign saturated evaporation pressure/temperature probe (PEu/tEu) - See /FA

8. TABLE OF PARAMETERS

8 = Serial probe 8
9 = Serial probe 9
10 = Serial probe 10
11 = Serial probe 11
12 = Control probe
13 = Virtual probe
14 = Set point
8 = Serial probe 8
9 = Serial probe 9
10 = Serial probe 10
11 = Serial probe 11
12 = Control probe
13 = Virtual probe
14 = Set point
Remote display
Present
Present
Optional
Optional
6 = Probe S6
7 = Probe S7
8 = Serial probe S8
9 = Serial probe S9
10 = Serial probe S10
11 = Serial probe S11
57
Pag.
Def
Min
Max
UoM
57
4
1
15
-
34
0
0
100
%
57
0
0
1
-
57
0
0
1
-
43
20
0
100
%
57
0
0
1
-
57
12
0
14
-
57
12
0
14
-
57
3
0
3
-
28
0
0
3
-
27
0
0
3
-
27
0
0
4
-
41
0
0
6
-
41
0
0
15
-
30
1
0
11
-
30
2
0
11
-
30
3
0
11
-
27-41
0
0
11
-
27-41
0
0
11
-
MPXPRO - + 0300055EN rel. 1.1 30/08/10
ENG
Type
Icon
A
C
A
A
NV
A
C
A
A
A
A
A
A
A
C
C
C
A
A

Hide quick links:

Advertisement

Table of Contents
loading