LED signal
Cause
Controller not
Orange fl ashing
compatible
Incorrect use of
Red fl ashing
the key
Orange steady
Data copy error
Key not powered
Off
or fault
The key can be programmed not only from the MPXPRO controller,
but also directly from a PC, using the special USB/I2C converter
(IRPOPZPRGO0) and the VPM program. Using this connection, the PC can
completely program the key. Specifi cally, the following operations are
possible: set the values of the parameters (both unit and operating), set
the visibility and upload attribute, write and read the parameters to/from
a fi le, and check the parameters.
2.11 Commissioning tool (VPM- Visual
Parameter Manager)
MPXPRO can communicate directly with a PC using the "commissioning"
port. This connection can be used to program and check the operation
of an MPXPRO controller from the PC when installing and fi rst starting the
system. The commissioning connection can be used to:
• set value, visibility and download attributes of all the parameters from
Master to Slave, including unit parameters;
• completely program a key;
• at start-up, monitor and manually control all the inputs/outputs;
• update the fi rmware.
A PC can access the commissioning connection via the special port
available on some user terminals code IR00UGC300 and remote display
code IR00XGC300 or in supervisory RS485 network.
The commissioning software can also be used to program the key.
Further information on the operation of the commissioning software is
available in the online manual for the VPM program, downloadable from
http://ksa.carel.com.
Meaning
Solution
The parameters
Check
cannot be
compatibility
copied due to
of the fi rmware
incompatibility
versions (see notes
of the fi rmware
above)
versions
Repeat the
The button on
procedure
the key has been
following the
released too early
instructions in
point c.
The data on the
Repeat the
controller or the
operation or
key may be corrupt
contact service
Check that the
--
key is powered or
contact service
Tab. 2.d
Commissioning via terminal/display (with IROPZTLN00
converter).
This is used to connect a supervisor PC, running the special software, to
an MPXPRO controller via a user terminal (IR00UGC300) or remote display
(IR00XGC300) fi tted with commissioning port. Identify the connection
port located under the keypad.
A
Terminal
IR00UGC300
IR00XGC300
Connect the USB ports on the converter and the PC using a USB cable.
If the PC is connected to a Master controller, the software can access
the unit and operating parameters and status variables relating to the
Master controller, as well as the Slave controllers in the subnetwork. If the
connection is made to the terminal on a slave, only the parameters (unit
and operating) and status variables of that Slave can be accessed.
Commissioning via the RS485 supervisor port (with
CVSTDUMOR0 converter)
As well as the connection via the terminal, MPXPRO can also be
connected to a PC via the RS485 supervisory network. In this case, the PC
will only be connected to the Master controller. Access to the parameters
(unit and operating) and status variables relating to the Slaves connected
to the Master will be available via the Master controller.
To use this commissioning connection:
• connect a Master controller (board terminals 20, 21, 22) to the RS485
output on the CVSTDUMOR0 converter, using an RS485 connection
cable;
• connect the USB ports on the converter and the PC using a USB cable.
Note: To manage the Slave controllers in the subnetwork from the
PC, make sure that these are correctly connected to the Master via
the tLAN.
MASTER
SLAVE
tLAN
RS485
CVSTDUMOR0
17
ENG
B
C
IROPZTLN00
USB/tLAN
converter
PC
Fig. 2.s
PC
USB
Fig. 2.t
MPXPRO - + 0300055EN rel. 1.1 30/08/10