easy way aria
easy way ARIA is the fi rst completely wireless CAREL solution for the
management of ambient comfort in buildings.
It guarantees energy saving and optimisation of the entire system.
User manual

Advertisement

Table of Contents
loading

Summary of Contents for Carel easy way aria

  • Page 1 ARIA is the fi rst completely wireless CAREL solution for the management of ambient comfort in buildings. It guarantees energy saving and optimisation of the entire system. User manual...
  • Page 3 The technical specifi cations shown in the manual may be changed without prior warning. The liability of CAREL in relation to its products is specifi ed in the CAREL general contract conditions, available on the website www.carel.com and/or by specifi c agreements with customers; specifi cally, to the extent where allowed...
  • Page 5: Table Of Contents

    5.4 Repeater variable list ......................34 6. TECHNICAL SPECIFICATIONS AND PRODUCT CODES 6.1 Terminal ..........................35 6.2 Sensor ..........................36 6.3 Access Point ........................37 6.3 Repeater ..........................38 7. WIRELESS FEATURES OF THE EASY WAY SYSTEM easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 7: Introduction

    ZigBee™ 1.3 Advantages of the CAREL solution Easy way ARIA is an advantageous solution in terms of: • fl exibility: possibility to manage fl exible spaces very simply, thus reorganising the layout of a supermarket or an offi ce without having an impact on the communication network.
  • Page 8: Application Examples

    Tab. 1.a The band centred around 2.45 GHz (used in the easy way ARIA system) is the only one that can be used all over the world, without needing to apply for special licenses. In addition, the ISM band (Industrial, Scientifi c and Medical) exploits the full potential of the standard, that is, can use 16 transmission channels with a bit rate of 250 kbit/s.
  • Page 9: Installation

    DC power supply. Important : If the same power supply is shared by more than one unit, connect the same wire from the transformer to the “–“ terminal of the power supply (1). easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 10: Configuration

    The following chapter describes an example of the procedure for setting • Set the desired CAREL network address using the 4 dipswitches (0 = the address, confi guring and connecting the devices for the creation of OFF; 1 = ON), as shown in the table.
  • Page 11 12= OFF. • If the sequence is not as indicated, reinitialise the device (see paragraph • Enter the desired CAREL network address for the parameter loc09; 3.5) • If the instrument is reinitialised, all the instruments associated with it will be disconnected and will need to be connected again.
  • Page 12: Connecting The Devices (Binding)

    The access point indicates that the connection has been made by Fig. 3.d sequentially activating the 3 LEDs . • CHECK: The sensor will be correctly associated if each time the button is pressed once the LED fl ashes once. easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 13: Reset Devices

    UOM typ ind. R/W note communicating with the access point. Number of sensors present Fig. 3.e easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 14: Wireless Variables

    -100dBm = poor signal -30dBm = strong signal Terminal and sensor supervisor variables par. description type index notes Battery level 100.0 Indicative wireless signal level -100.0 -30.0 Minimum supervisor transmission time Tab. 3.f easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 15: Terminal

    11 Time band active (1 or 2) indicator 12 Sleep mode indicator. The digit shows the hours remaining 13 Lock button/function active 14 Active alarm. Field 8 shows “E” + alarm code 1 to 255 easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 16 17 manual only limited to cooling (sun) heating (snow) access manual only limited to cooling (sun) manual only limited to heating Sleep timer setting easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 17 Note: from when programming until the expiry of the fi rst band, only the symbol without indicating the number of the Select HOUR, MINUTES and ON/OFF/TEMP fi elds active band. Set the value of the fi eldsi easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 18 Time band index from the supervisor, if D12 active no time band symbol displayed time band 1 symbol displayed time band 2 symbol displayed Sleep mode status instrument not in sleep mode instrument in sleep mode Tab. 4.d easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 19 • By time, 5 seconds after the last button is pressed • manually by pressing the button. Display and/or set from the supervisor par. description type index notes Fresh Air percentage easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 20 “---“. • the humidity set point can also be displayed/set on the temperature- only model. Example: with the default value on the temperature plus humidity model. Fig. 4.c.g easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 21: Functions

    “---” if humid. sensor not fi tted Set Humidity Clock Default Tab. 4.i par. description type index notes loc 1 Field shown on main display loc 2 Field shown on secondary display Tab. 4.j easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 22 5 Ambient temperature sensor calibration -9.5 +9.5 °C loc 6 Ambient humidity sensor calibration Tab. 4.l easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 23 23.0 °C. Fig. 4.d.k In this case the current working set point will be 23-2.5 = 20.5 °C Note: the function is not active in FAN mode. Fig. 4.d.j easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 24 N = time (in minutes) that the function is activated after pressing a button. Occup. status = 0 Occup. status = 1 After a time equal to the Occupancy time (min) easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 25 °C Diff Heating/cooling algorithm diff erential 10.0 °C Dead band for temperature calculation algorithm in AUTO 25.0 °C mode Value calculated for heating request Value calculated for cooling request Tab. 4.p easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 26 (manual dehumidifi cation), irrespective of the set point and humidity reading. • RD = 1 Fig. 4.d.s Fig. 4.d.t • RU = 0 easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 27: Alarms

    Alarm code from the supervisor no active alarm alarm code contained in the variable Example: if the parameter is set to 173 the terminal will display. Fig. 4.e.b easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 28: Setting The Parameters

    °C/°F or %rH Tab. 4.t To exit parameter programming mode: • By time, 30 sec after the last button was pressed • manually by pressing the button Editing the user parameters Fig. 4.f.b easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 29 Wait for the terminal to complete transmission to the access point (antenna symbol fl ashing). Nota: After the change has been set, the factory parameters can only be accessed using the new password. easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 30 17 manual only limited to cooling (sun) heating (snow) manual only limited to cooling (sun) manual only limited to heating Sleep timer setting easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 31 Tab. 4.u * = this parameter can only be set/displayed with access by password. T&H = Temperature/humidity model EW00TB T = Temperature only model EW00TA* easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 32: Supervisor

    ON/OFF terminal off terminal on Sleep mode status instrument not in sleep mode instrument in sleep mode Occupancy mode status deactivated active Humidifi cation request request not active request active easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 33 Humidity set point Temperature value Humidity value Field shown on secondary display no display Humidity set point loc 2 temperature set point Humidity value Temperature value display clock easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 34: Sensor Variable List

    CAREL address of the device Minimum supervisor transmission time Tab. 5.c 5.4 Repeater variable list There is no list of supervisor variables for the repeater. easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 35: Technical Specifications And Product Codes

    SAFT LS 14500 lithium battery Maximum power input 130 mW Battery life in normal operating conditions 4 years (CAREL is not responsible for the specifi ed battery life) Radio frequency specifi cations Frequency: selectable 2405 to 2480 MHz Power transmitted: 0 dBm...
  • Page 36: Sensor

    Maximum power input 100 mW Battery life in normal operating conditions From 3 to 8 years according to set transmission time. (CAREL is not responsible for the specifi ed battery life) Radio frequency specifi cations Frequency: selectable 2405 to 2480 MHz...
  • Page 37: Access Point

    This is the coordinator of a wireless network as well as the gateway for the information between the ZigBee™ protocol and the CAREL side (pCO or PlantVisor). Up to 15 access points can be connected to the same fi eld serial port.
  • Page 38: Repeater

    Observe local legislation for the disposal of electrical material Tab. 6.d Note: The index of protection is maintained only if the cable used has outside cross-section of less than 8 mm. easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 39 • The distance between the access point and the terminal/sensor is greater than 50 m, with visibility between the devices. Fig. 6.j.a Fig. 6.i.a Fig. 6.j.b Fig. 6.i.b easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 40: Wireless Features Of The Easy Way System

    8 Repeaters, connectable directly to the access point; – 24 terminals/sensors, connectable directly to each repeater. Example: Fig. 7.a Key: Access Point 1st level dominion Repeater 2nd level dominion terminals/sensors 3th level dominion easy way ARIA +030220841 - rel. 1.0 - 26.10.2007...
  • Page 41 Notes...
  • Page 42 Note...