2
2.3 E
V driver expansion board
(MX3OPSTP**): terminals and connections
The input of the load 0 to 10 Vdc must
E
E
2
2
V Driver
V Driver
feature reinforced insulation with
reference to its internal power supply
Tight screw and nut after
installing connector/cable and E
CAREL E2VCABS*
Green 84
Brown/Red 83
Yellow/Black 82
White 81
Shield 80
Valve cable lenght without solenoid
Unique correct
connection view
(no other possible
connections).
E2VCON* not suitable
for refrigeration
application.
For further information, please refere to the "EEV system guide"
(code +030220810) available in the web site www.carel.com, in the
literature section.
Fig. 2.g
Terminal
Description
0 to 10 Vdc output,
Control signal for modulating actuators:
73
4.5 mA MAX
Maximum error 2% f.s., maximum load 2.2 KΩ
74
GND
75
Functional earth
80
Shield
81
White
Connection to CAREL
82
Yellow/black
E2VCABS600
83
Brown/red
84
Green
Important:
• To connect the valve, use a CAREL shielded cable code E2VCABS*00
(AWG22) or an alternative suitably sized 4-wire shielded cable:
- reverse valve or valve size > = E3V45 -> solenoid required with
AWG22 shielded cable
- direct valve and valve size < E3V45 -> if the solenoid is installed
AWG22 shielded cable, if the solenoid is not installed, for the size of
the cables see the table to the side.
• the input of the 0 to 10 Vdc modulating actuator load must have
reinforced insulation, based on its internal power supply.
GND
0 to10 Vdc
73 74
Analogic
10
GND
output only for
Vdc
MX3OPST(H,U)0*
MX3OPST(H,U)*
2
V.
connection cable
2
CAREL E
V
GR BR
YE WH
75
Shield
1 3
2 4 5
84
83
82
81
80
Valve cable lenght without solenoid
L < 10m
AWG22
L < 30m
AWG20
L < 50m
AWG18
2
E
V
valve with shielded cable
Tab. 2.a
2.4 PWM driver expansion board
(MX3OPPWM**): terminals and connections
PWM Driver
PWM valve
115-230 Vac
20 W max 5 W min
POWER SUPPLY
N
115-230 Vac
L
25 W max
60 61
L
MX2OPPWM*
Fuse 0.25 AT
Earth
Analogic
output only for
MX2OPPWM0*
Terminal
60
L
61
N
62
N
63
L
64
+
65
-
66
Not used
67
0 to 10 Vdc output
68
GND
Note:
• use either AC or DC PWM valves;
• the input of the 0 to 10 Vdc modulating actuator load must have
reinforced insulation, based on its internal power supply.
Important: do not use PWM valves with rectifi ed 230 Vac power
supply.
2.5 Expansion board 0 to 10 Vdc output
(MX3OPA1002): terminals and connections
Analog 0 to 10 Vdc
MX2OPA1002
Analog
10
GND
Vdc
output
42
41
Terminal
40
Not used
41
0 to 10 Vdc output
42
GND
Note: the input of the 0 to 10 Vdc modulating actuator load must
have reinforced insulation, based on its internal power supply.
13
DC/AC output
PWM valve
115 Vdc RMS-230 Vdc RMS
PWM
PWM
20 W max 5 W min
ac
dc
+
N L
Use
62 63
64 65
PWMac or PWMdc
N
PWM
AC
PWM
DC
+
-
N
L
valves alternatively
10
GND
Vdc
68
67
66
0 to 10 Vdc
The output 0 to 10 Vdc must feature
reinforced insulation with reference
GND
to its internal power supply
Fig. 2.h
Description
Power supply:
115 to 230 Vac, 50/60 Hz, 25 VA MAX
Power supply PWM valve Vac:
115 to 230 Vac, 50/60 Hz, 5 W MIN, 20 W MAX
Power supply PWM valve Vdc:
105 to 230 Vdc RMS, 5 W MIN, 20 W MAX
Control signal for modulating actuators:
Maximum error 2% f.s., maximum load 2.2 KΩ.
40
0 to 10 Vdc
The output 0 to 10 Vdc must feature
reinforced insulation with reference
to its internal power supply.
GND
Fig. 2.i
Description
Control signal for modulating actuators: Maximum
error 2% f.s., maximum load 2.2 KΩ.
MPXPRO - + 0300055EN rel. 1.1 30/08/10
ENG
Tab. 2.b
Tab. 2.c