Carel MPXPRO User Manual page 48

Electronic controller
Hide thumbs Also See for MPXPRO:
Table of Contents

Advertisement

ENG
Defrost Running time (parameters d10, d11)
Running time is a special function that determines when the refrigeration
unit needs defrosting. In particular, it is assumed that if the evaporator
temperature measured by probe Sd remains continuously below a
certain set threshold (d11) for a certain time (d10), the evaporator may
be frozen and a defrost is activated. The time is reset if the temperature
returns above the threshold.
Par.
Description
d10
Defrost time in "Running time" mode
0 = function disabled
d11
Defrost temperature threshold in "Running
time" mode
dt1
End defrost temperature (read by Sd)
dt2
End defrost temperature (read by Sd2)
d1
Sd
d11
ON
DEF
OFF
Key
Sd
Defrost probe
DEF
Defrost
Important : for multiplexed hot gas defrosts, the setting is only
valid on the Master and the defrost is synchronized across the
Master/Slave network.
Pressure probe alarm management during defrost
(parameter d12)
During defrost and dripping, so as to avoid false pressure probe error
signals, errors are ignored. The supervisor update can also be disabled.
Par.
Description
d12
Pressure probe alarm management during
defrost
probe error
supervisor update
0
disabled
1
enabled
2
disabled
3
enabled
MPXPRO - + 0300055EN rel. 1.0 30/08/10
Def
Min
Max
0
0
240
-30
-50
50
8
-50.0
50.0
8
-50.0
50.0
Tab. 6.g.i
t
t
d10
Fig. 6.k
t
Time
Def
Min
Max
0
0
3
enabled
enabled
disabled
disabled
Tab. 6.g.j
Sequential stops (parameters dS1, dS2)
Par.
Description
dS1
Compressor off time in "Sequential stop"
defrost mode
dS2
Compressor operating time in "Sequential
stop" defrost mode
Sequential stop mode is especially useful for high-normal temperature
UoM
refrigeration controllers, and is based on the intelligent stopping of
min
control to allow the evaporator to defrost naturally by the fl ow of
ambient air only, without activating the defrost output and consequently
°C/°F
the defrost heaters. If the function is enabled (parameter dS1>0), two
counters are activated:
°C/°F
• OFFTIME: counts down during the stop time and on hold during
°C/°F
control;
• ONTIME: counts down during control and on hold during the stop
time.
Two events may occur, with reference to the following fi gure:
1. OFFTIME is reset (instant C): OFFTIME and ONTIME are reset with
dS1 and dS2 value and the defrost is considered completed. Control
resumes;
2. ONTIME is reset (instant A): OFFTIME is reset with the default value
and the natural defrost starts, lasting the time dS1. At the end of the
defrost (instant B), OFFTIME and ONTIME are reloaded with dS1 and
dS2 value and control resumes;
1
ON
CMP
OFF
2
ON
CMP
OFF
Key
UoM
CMP
Compressor
-
The purpose is to stop control and allow natural defrosts only when
necessary.
Note: the setting of parameter F3 has no eff ect. Evaporator fan
management depends on parameter F0.
Skip defrost (parameters d7, dn)
The function applies to defrosts that end by temperature, otherwise it
has no eff ect. The Skip defrost function evaluates whether the defrost
duration is less than a certain threshold dn1 (dn2) and based on this
establishes whether or not the following defrosts will be skipped.
Par.
Description
d7
Skip defrost
0 = disabled; 1 = enabled;
dn
Nominal defrost duration for "Skip defrost"
dP1
Maximum defrost duration
dP2
Maximum secondary evaporator defrost
duration
48
Def
0
120
OFFTIME=0
regulation
regulation
C
ONTIME=0
regulation
defrost
dS1
A
B
Fig. 6.l
t
Time
Def
0
75
45
45
Min
Max
UoM
0
45
min
0
240
min
Tab. 6.g.k
t
t
regulation
t
Min
Max
UoM
0
1
-
0
100
%
1
240
min
1
240
min
Tab. 6.g.l