Technical Specifications - Carel MPXPRO User Manual

Electronic controller
Hide thumbs Also See for MPXPRO:
Table of Contents

Advertisement

Model
MX3xxxxHxx
Power supply
MX3xxxx(3,5,6)Hxx
Insulation guaranteed by the
MXxxxxx(E,A)xx
power supply
S1, S2 and S3
S4/DI1, S5/DI2
S6/ DI3
Inputs
S7/DI4
DI5
Maximum distance between probes and digital inputs less than 10 m. Note: in the installation it is recommended to separate the power
and load connections from the probe, digital input, display and supervisor cables.
Std. CAREL NTC
Std. CAREL PTC
(specifi c model)
Pt 1000
Probe type
NTC L243
0 to 5 V ratiometric
4 to 20 mA
0 to 10 V
according to the model
Relay outputs
R1, R5, R4
insulation from very low voltage parts
insulation between independent relay outputs
Model
Analogue outputs PWM 1, 2
MXxxx(2, 3)xxxx
Type of connections
model
Connections
MXxxxxxx(A,G,M)x
MXxxxxxx(C,I,O)x
The correct sizing of the power cables and the connections between the instrument and the loads is the installer's responsibility.
Clock
Operating temperature
Index of protection
Operating humidity
Storage temperature
Storage humidity
Environmental pollution
PTI of the insulating materials
Period of stress across the insulating parts
Category of resistance to fi re
Class of protection against voltage surges
Type of action and disconnection
Construction of the control device
Classifi cation according to protection against electric shock Class 2 when suitably integrated
Device designed to he hand-held or integrated into
equipment designed to be hand-held
Software class and structure
Cleaning the front panel of the instrument
Main and secondary display
Maximum distance between controller and display
LAN connection
Serial communication (master only)
Programming key

10. TECHNICAL SPECIFICATIONS

Voltage
110-230 V~ , 50/60 Hz
110-230 V~ , 50/60 Hz
insulation from very low voltage parts
insulation from relay outputs
NTC (MXxxxx0xxx) or NTC, PTC, PT1000 and NTC L243 (MXxxxx(1,2,3,4.5,6,7,8)xxx)
NTC (MXxxxx0xxx) or NTC, PTC, PT1000 and NTC L243 (MXxxxx(1,2,3,4.5,6,7,8)xxx)
voltage-free contact, contact resistance < 10 Ω, closing current 6 mA
NTC (MXxxxx0xxx) or NTC, PTC, PT1000 and NTC L243 (MXxxxx(1,2,3,4.5,6,7,8)xxx)
0 to 5 V ratiometric (MXxxxxxxxx)
voltage-free contact, contact resistance < 10 Ω, closing current 6 mA
NTC (MXxxxx0xxx) or NTC, PTC, PT1000 and NTC L243 (MXxxxx(1,2,3,4.5,6,7,8)xxx)
0 to 5 V ratiometric (MXxxxxxxxx), 4 to 20 mA, 0...10 V (MXxxxx(1,2,3,4.5,6,7,8)xxx)
voltage-free contact, contact resistance < 10 Ω, closing current 6 mA
voltage-free contact, contact resistance < 10 Ω, closing current 6 mA
10 kΩ at 25 °C, range from –50 °C to +90 °C
measurement error
985 Ω a 25°C, range from -50 °C to 150 °C
1000Ω a 0 °C, range from –50 °C to +90 °C
measurement error
2000 Ω a 0 °C, range from -50 °C to 90 °C
measurement error
resolution 0.1 % fs
measurement error
resolution 0.5 % fs
measurement error
resolution 0.1 % fs
measurement error
EN60730-1
relay
250 V~
6 (4) A on N.O. 6 (4) A on N.C. 2 (2) A on
N.O. and N.C.
R3
8 (2) A on N.O. and N.C.
R2
10 (10) A
reinforced
6mm in air, 8mm on surface
3750V insulation
primary
3mm in air, 4mm on surface
1250 V insulation
Output voltage, maximum current available (not isolated from board earth)
12 Vdc, 20 mA max for each PWM
relay
screw 180°
plug-in 180°
error at 25°C
error in the temp. range –10T60 °C
ageing
Discharge time
Recharge time
MXxxxxxx(A,B,C,G,I)x
MXxxxxxx(M,N,O)x
IP00
<90% RH non-condensing
-20T70 °C
<90% RH non-condensing
2 (normal)
printed circuits 250, plastic and insulating materials 175
long
category D and category B (UL 94-V0)
category II
1C relay contacts (microswitching)
integrated electronic control device
no
Class A
only use neutral detergents and water
External
up to 10 m with shielded cable AWG22 (power supply, rx-tx, gnd)
up to 100 mt (only one terminal can be connected) with shielded cable AWG20 (power supply, rx-tx, gnd)
up to 100 m total, with shielded cable AWG20 (rx-tx, gnd);
RS485, CAREL and Modbus® protocols (auto-recognized), 19200 bps, 8 data bits, no parity, 2 stop bits
available on all models
Power
11.5 VA, 50 mA~ max
23 VA, 115V~ (200 mA) 230V~ (100 mA) max
reinforced
6mm in air, 8mm on surface
3750 V insulation
primary
3mm in air, 4mm on surface
1250 V insulation
1 °C in range from –50 °C to +50 °C; 3 °C in range from +50 °C to +90 °C
2 °C in range from –50 °C to +50 °C; 4 °C in range from +50 °C to +150 °C
3 °C in range from –50 °C to 0 °C; 5 °C in range from 0 °C to +90 °C
2 °C in range from –50 °C to +25 °C
2 % fs maximum; 1 % typical
8 % fs maximum; 7 % typical
9 % fs maximum; 8 % typical
operating cycles
100000
100000
100000
power supply
probes
screw 180°
screw 180°
plug-in 180°
plug-in 180°i
67
UL 873
250 V~
operating cycles
6A res 2FLA 12LRA
8A res 5FLA 30LRA
10A res 10FLA 60 LRA
Cross-section
Maximum current
for cables from 0.5 to 2.5
12 A
2
mm
± 10 ppm (±5.3 min/year)
- 50 ppm (-27 min/year)
< ±5 ppm (±2.7 min/year)
6 months typical (8 months maximum)
5 hours typical (< 8 hours maximum)
-10T60 °C
-10T50 °C
MPXPRO - + 0300055EN rel. 1.1 30/08/10
ENG
30000
30000
30000

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents