800b050a-1e81xxxx
Non-redundant:Insufficient Resources for [RedundancySetElementName] has asserted. (Fan
Zone 1)
Explanation: This message is for the use case when a Redundancy Set has transitioned to Non-
redundant:Insufficient Resources.
May also be shown as 800b050a1e81xxxx or 0x800b050a1e81xxxx
Severity: Error
Alert Category: Critical - Fan Failure
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0810
SNMP Trap ID: 11
Automatically notify Support: No
User response:
1.
Make sure that the connectors on fan n are not damaged.
2.
Make sure that the fan n connectors on the system board are not damaged.
3.
Make sure that the fans are correctly installed.
4.
Reseat the fans.
Replace the fans. (n = fan number)
5.
800b050a-1e82xxxx
Non-redundant:Insufficient Resources for [RedundancySetElementName] has asserted. (Fan
Zone 2)
Explanation: This message is for the use case when a Redundancy Set has transitioned to Non-
redundant:Insufficient Resources.
May also be shown as 800b050a1e82xxxx or 0x800b050a1e82xxxx
Severity: Error
Alert Category: Critical - Fan Failure
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0810
SNMP Trap ID: 11
Automatically notify Support: No
User response:
1.
Make sure that the connectors on fan n are not damaged.
2.
Make sure that the fan n connectors on the system board are not damaged.
3.
Make sure that the fans are correctly installed.
4.
Reseat the fans.
5.
Replace the fans. (n = fan number)
800b050a-1e81xxxx • 800b050a-1e82xxxx