(Function mode 1)
Display
Function
sequence
No.
16
F-23
Electronic thermal
thermal
(NOTE 2) free setting
17
F-24
Overload restriction
restriction level setting
18
F-25
NOTE 1: When MD0 is set and the input terminal SFT is turned ON, the data of all functions is locked. When MD2 is
set (stored), the data of all the functions is locked. During locking, no data can be changed. MD1, MD3
can set only the output frequency.
NOTE 2: Electronic thermal characteristic free setting current and frequency depends on the inverter rating.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
(Function mode 2)
Function
Initialization display
name
contents
Electronic
E-THM A1
characteristic
current (1)
Electronic
E-THM F1 0000 Hz
thermal
characteristic
free setting
frequency (1)
Electronic
E-THM A2
thermal
charac teristic
free setting
current (2)
Electronic
E-THM F2
thermal
characteristic
free setting
frequency (2)
Electronic
E-THM A3
13.0 A
thermal
characteristic
free setting
current (3)
Electronic
E-THM F3
thermal
characteristic
free setting
frequency (3)
Overload
OLOAD LEVEL125%
Overload
OLOAD CONST01.0
restriction
constant
setting
Valid
OLOAD ACC
selection
for overload
restriction
acceleration
Software
S-LOCK
lock
selection
Initialization
8.5A
Rated capacity of
each inverter
Rated capacity of
each inverter
8.5A
Rated capacity of
each inverter
5 Hz
Rated capacity of
each inverter
Rated capacity of
each inverter
73 Hz
Rated capacity of
each inverter
125%
1.0
ON
ON
MD1
MD1
12-9
Setting, change
Setting contents
contents
0 to 600.0 A
0 to 400 Hz
0 to 600.0 A
0 to 400 Hz
0 to 600.0 A
0 to 400 Hz
50 to 150%
Under the sensorless vector
control, an overload is detected
from both the overload restric-
tion and torque limiter.
0.3 to 31.0
When the setting is 31.0 in SLV
or V2 control mode, the
overload restriction has no
effect.
ON: Valid for
Even if the function is set to
acceleration
OFF, the overload restriction is
Keep the
invalid only for the first
function ON
acceleration when the forward
for operation.
and reverse run command is
turned on.
MD0/MD1
MD0, MD1: Terminal software
MD2/MD3
lock (SFT)
MD2, MD3: Software lock
(NOTE 1)