Table 5. Alert Codes and Troubleshooting
Alert
Priority
Alert Text
Code
275
Critical
(Furnace) The furnace flame is out of sequence.
276
Critical
(Furnace) The furnace is not able to calibrate or
the high pressure switch opened or failed to
close in run mode.
290
Critical
(Furnace) There is a problem with the furnace
ignition circuit.
291
Critical
(Furnace) The heating airflow is below the mini-
mum required level.
292
Critical
(Furnace / Air Handler) The (furnace or air−han-
dler) indoor blower motor will not start.
294
Critical
(Furnace) There is over current in the furnace
inducer motor.
295
Minor
(Furnace) The indoor blower motor is over heat-
ing.
310
Critical
(Furnace / Air Handler) There is a problem with
(furnace or air−handler) discharge air sensor.
311
Minor
(Furnace) The heat firing rate has been reduced
to match available airflow (cutback mode).
312
Minor
(Furnace / Air Handler) The blower cannot pro-
vide the requested CFM due to high static.
313
Minor
(Furnace / Air Handler) The indoor and outdoor
unit capacities do not match.
344
Critical
(Furnace) Relay Y1 Failure
506920−01 09/12
Critical alerts are displayed on Home (user) screen, in the Homeowner alert button, and in the Installer
alert button. Minor and Moderate alerts are found only in the Installer alert button.
Steps to clear
The system will go into Watchguard mode. Shut off gas. Check for gas valve leak. The alarm/fault
will clear on next successful ignition.
The system will go into Watchguard mode. Check vent system and pressure
switch wiring connections. The fault/alarm will clear when the furnace calibrates itself successfully.
The system will go into Watchguard mode. Measure resistance of hot surface igniter. Replace the hot
surface ignitor it is not within specifications. The alarm/fault will clear on next successful ignition.
The system will go into Watchguard mode. Check for dirty filters and other air flow restrictions. Check
blower performance. The alarm/fault will clear when a heat call ends successfully.
The system will go into Watchguard mode. Indoor blower motor unable to start. This could be due to
seized bearing, stuck wheel, obstruction etc. Replace motor or wheel if assembly does not operate or
meet performance standards. The alarm/fault clears after the indoor blower motor starts successfully.
The system will go into Watchguard mode. Check combustion blower bearings, wiring and amps.
Replace if does not operate or does not meet performance standards. The alarm/fault clears after
inducer current is sensed to be in−range after the ignition following the Watchguard mode or reset.
Indoor blower motor over temperature (motor tripped on internal protector). Check motor bearings
and amps. Replace if necessary. The alarm/fault clears after blower demand is satisfied.
Compare outdoor sensor resistance to temperature/resistance charts in installation instructions.
Replace sensor if necessary. The alarm/fault is cleared 30 seconds after fault is detected as recov-
ered.
Warning Only. Furnace blower in cutback mode due to restricted airflow. Reduce firing rate every 60
seconds to match available CFM. Check filter and duct system. To clear, replace filter if needed or
repair/add duct. 2−stage controls will reduce firing rate to 1st stage. The alarm/fault clears when a
heat call finishes successfully.
Warning Only. Restricted airflow − Indoor blower is running at a reduced CFM (Cutback Mode − The
variable speed motor has pre−set speed and torque limiters to protect the motor from damage caused
by operating outside of design parameters (0 to 0.8" e.g.. total external static pressure). Check filter
and duct system. To clear, replace filter if needed or repair/add duct. The alarm/fault is cleared after
the current service demand is satisfied.
Check for proper configuring in installation instructions. Alarm is just a warning. The system will
operate, but might not meet efficiency and capacity parameters. The alarm will clear after commis-
sioning is complete.
Y1 relay failed; operation stopped. Alarm clears 300 seconds after Y1 input sensed OFF.
Page 50
table continued on next page