Installation (for qualified installers only)

Clearances

Due to the high temperature of the heater, it should be located out of traffic and away from furniture and
draperies.
Side
k
Wall
\

Mantel Clearances

The maximum mantel depth is 12".
NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it
does, it is considered a mantel and must meet the mantel requirements listed in this manual.
Above Base of Insert (n)
© Travis Industries
n
m
l
37+"
36"
35"
Mantel Height
34"
33"
32"
31"
k Sidewall to Insert
l Side Facing
(non-combustible)
m Top Facing*
(non-combustible)
n Mantel*
(combustible or
non-combustible)
x Hearth Extension
(3-Piece Panel)
x Hearth Extension
(1-Piece Panel)
* Measured from the base of the insert.
x
NOTE: the non-combustible top facing
must extend 35.5" (902mm) above the
base of the insert or to the bottom of the
mantel (whichever is less).
Maximum Mantel Depth
0" 1" 2" 3" 4" 5" 6" 7" 8" 9" 10" 11" 12"
4091008
Minimum
Clearances
4"
102mm
4"
102mm
35.5"
902mm
35.5"
902mm
1.25"
32mm
0"
0mm
100-01236_000