GE D.20 RIO Hardware User Manual page 35

Distributed i/o controller
Table of Contents

Advertisement

D.20 RIO Distributed I/O Controller
Chapter 4: Setting Up the D.20 RIO
D.20 RIO - HARDWARE USER'S MANUAL
Setting Up the D.20 RIO
There are two software components of the D.20 RIO:
Online HMI: A web-based interface that is used to configure connections to peripheral
clients, edit client map files, configure system options, and view point status
D.20 RIO Configuration Utility: A command-line utility that is used to configure device
parameters
D.20 RIO devices communicate natively only with D400 firmware version 3.20 or higher.
Users planning on connecting an existing D400 units to a D.20 RIO must contact GE
Customer Service to either upgrade hardware through the RMA process or use the
Upgrade Manager. D400 upgrade kits are also available for order though GE Digital
Energy's Online store.
Table 14 indicates the compatibility between D400 and D.20 RIO firmware versions.
Table 14: D400 and D.20 RIO firmware version compatibility
D.20 RIO
D400 Firmware
Firmware Version
Version
V1.00
V3.20
V1.10
V3.20*
V1.00
V4.10
V1.10
V4.10
* The D400 V3.20 requires service update 320_087_20130509_IRIGB_1MS.
Refer to the D400 Substation Gateway Software Configuration Guide (GE part number
SWM0066) and the online help for assistance in configuring a D400 device to
communicate with your D.20 RIO.
Compatibility
Yes
Yes
Note: D400 V3.20 does not support D.20 RIO
redundancy.
No
Yes