Low Pressure Protection Control - Daikin REYQ72 Serveice Manual

R-410a heat recovery 60hz
Table of Contents

Advertisement

Protection Control
4.2

Low Pressure Protection Control

This low pressure protection control is used to protect compressors against the transient
decrease of low pressure.
[In cooling operation]
Low pressure not limited
Pe<50 psi
Low pressure limited
All STD compressors
Pe<36 psi
Master unit:52 Hz + OFF
Slave unit:Stop
Pe<10 psi
Low pressure standby
[In heating operation]
Pe<23 psi
124 Hz + OFF
Pe<23 psi
Pe<19 psi
52 Hz + OFF
60
Pe>58 psi
stop.
Low pressure not limited
&
Low pressure limited
Pe<10 psi
Low pressure standby
Pe: LP pressure sensor detection
value for master unit
When occurring 3 times within 30 min.,
the malfunction code " E4 " is output.
Pe: LP pressure sensor detection
value for each outdoor unit
Pe >36 psi
INV upper limit frequency = 210 Hz
Pe>28 psi
INV upper limit frequency: 1-step /
20 sec up from current compressor
frequency
When occurring 3 times within 30 min.,
the malfunction code "E4" is output.