Ac Reactors, Input Side; Ac Reactors, Output Side; Examples Of These Situations Include - Hitachi SJ200 Series Instruction Manual

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for SJ200 Series:
Table of Contents

Advertisement

Component Descriptions

AC Reactors, Input Side

This is useful in suppressing harmonics induced on the power supply lines, or when the
main power voltage imbalance exceeds 3% (and power source capacity is more than
500 kVA), or to smooth out line fluctuations. It also improves the power factor.
In the following cases for a general-purpose inverter, a large peak current flows on the
main power supply side, and is able to destroy the inverter module:
• If the unbalanced factor of the power supply is 3% or higher
• If the power supply capacity is at least 10 times greater than the inverter capacity (the
power supply capacity is 500 kVA or more)
• If abrupt power supply changes are expected

Examples of these situations include:

1. Several inverters are connected in parallel, sharing the same power bus
2. A thyristor converter and an inverter are connected in parallel, sharing the same
power bus
3. An installed phase-advance (power factor correction) capacitor opens and closes
Where these conditions exist or when the connected equipment must be highly reliable,
you MUST install an input-side AC reactor of 3% (at a voltage drop at rated current)
with respect to the supply voltage on the power supply side. Also, where the effects of an
indirect lightning strike are possible, install a lightning conductor.
Example calculation:
V
= 205V, V
RS
where V
is R-S line voltage, V
RS
Unbalance factor of voltage
Please refer to the documentation that comes with the AC reactor for installation instruc-
tions.

AC Reactors, Output Side

This reactor reduces the vibrations in the motor caused by the inverter's switching
waveforms, by smoothing the waveforms to approximate commercial power quality. It is
also useful to reduce the reflected voltage wave phenomenon when wiring from the
inverter to the motor is more than 10m in length. Please refer to the documentation that
comes with the AC reactor for installation instructions.
= 203V, V
= 197V,
ST
TR
is S-T line voltage, V
ST
Max. line voltage (min.) Mean line voltage
-----------------------------------------------------------------------------------------------------------
=
(
V
V
V
+
RS
RS
ST
------------------------------------------------------------------ -
=
(
V
V
+
+
RS
ST
SJ200 Inverter
is T-R line voltage
TR
Meanline voltage
) 3 ⁄
V
+
205 202
TR
×
100
----------------------- -
=
) 3 ⁄
V
TR
5–3
×
100
×
100
1.5%
=
202

Advertisement

Table of Contents
loading

Table of Contents