Hitachi SJ200 Series Instruction Manual page 111

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for SJ200 Series:
Table of Contents

Advertisement

"B" Function
Func.
Name /
Code
SRW Display
B088 Restart mode after FRS Selects how the inverter
RUN FRS
B090 Dynamic braking usage
ratio
BRD %ED
0000.0%
B091 Stop mode selection
STP Slct
B092 Cooling fan control
FAN-CTRL
OFF
B095 Dynamic braking
control
BRD Slct
OFF
B096 Dynamic braking
activation level
BRD LVL
00360V
B130 Over-voltage
LADSTOP enable
OVLADSTOP
B140 Over-current trip
suppression
I-SUP Mode
Description
resumes operation when the
ZST
free-run stop (FRS) is
cancelled, two options:
00... Restart from 0Hz
01... Restart from frequency
detected from real speed of
motor (frequency matching)
Selects the rate of use (in %) of
the regenerative braking
resistor per 100 sec. intervals,
range is 0.0 to 100.0%
0% . Dynamic braking disabled
>0% Enabled, per value
Selects how the inverter stops
the motor, two option codes:
DEC
00... DEC (decelerate and stop)
01... FRS (free run to stop)
Selects when the fan is ON per
inverter operation, two options:
00... Fan is always ON
01... Fan is ON during run,
OFF during stop (5 min.
delay from ON to OFF)
02... Fan is temperature-
controlled
Three option codes:
00... Disable
01... Enable during RUN only
02... Enable always
Range is:
330 to 380V (200V class),
660 to 760V (400V class)
Pauses deceleration ramp when
DC bus voltage rises above
threshold level, in order to
OFF
avoid over-voltage trip.
Two option codes:
00... Disable
01... Enable
Two option codes:
00... Disable
01... Enable
OFF
SJ200 Inverter
Defaults
Run
Mode
–FEF
–FU
Edit
(EU)
(USA)
00
00
0.0
0.0
00
00
00
00
00
00
360/
360/
720
720
00
00
00
00
3–39
Units
%