Hitachi SJ200 Series Instruction Manual page 116

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for SJ200 Series:
Table of Contents

Advertisement

3–44
"C" Group: Intelligent Terminal Functions
Option
Terminal
Code
Symbol
13
USP
15
SFT
16
AT
18
RS
19
PTC
20
STA
21
STP
22
F/R
23
PID
Input Function Summary Table
Function Name
Unattended Start
ON
Protection
OFF
Software Lock
ON
OFF
Analog Input
ON
Voltage/current
Select
OFF
Reset Inverter
ON
OFF
PTC Thermistor
ANLG When a thermistor is connected to terminals [6]
Thermal Protection
OPEN
Start
ON
(3-wire interface)
OFF
Stop
ON
(3-wire interface)
OFF
FWD, REV
ON
(3-wire interface)
OFF
PID Disable
ON
OFF
Description
On powerup, the inverter will not resume a Run
command (mostly used in the US)
On powerup, the inverter will resume a Run
command that was active before power loss
The keypad and remote programming devices
are prevented from changing parameters
The parameters may be edited and stored
Terminal [OI] is enabled for current input (uses
terminal [L] for power supply return)
Terminal [O] is enabled for voltage input (uses
terminal [L] for power supply return)
The trip condition is reset, the motor output is
turned OFF, and powerup reset is asserted
Normal power-ON operation
and [L], the inverter checks for over-
temperature and will cause trip event and turn
OFF output to motor
A disconnect of the thermistor causes a trip
event, and the inverter turns OFF the motor
Starts the motor rotation
No change to present motor status
Stops the motor rotation
No change to present motor status
Selects the direction of motor rotation: ON =
FWD. While the motor is rotating, a change of
F/R will start a deceleration, followed by a
change in direction.
Selects the direction of motor rotation: OFF =
REV. While the motor is rotating, a change of F/
R will start a deceleration, followed by a change
in direction.
Temporarily disables PID loop control. Inverter
output turns OFF as long as PID Enable is active
(A071=01).
Has no effect on PID loop operation, which
operates normally if PID Enable is active
(A071=01).

Advertisement