Thermistor Thermal Protection - Hitachi SJ200 Series Instruction Manual

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for SJ200 Series:
Table of Contents

Advertisement

Thermistor Thermal Protection

Motors that are equipped with a thermistor can be protected from overheating. Input
terminal [6] has the unique ability to sense a thermistor resistance. When the resistance
value of the thermistor connected to terminal [TH] (6) and [L] is more than 3 k Ω ±10%,
the inverter enters the Trip Mode, turns OFF the output to the motor, and indicates the
trip status E35. Use this function to protect the motor from overheating
Option
Terminal
Code
Symbol
19
TH
Thermistor Thermal
Protection
C006 only
Valid for inputs:
C085
Required settings:
Notes:
Be sure the thermistor is connected to terminals [6]
and [L]. If the resistance is above the threshold the
inverter will trip. When the motor cools down
enough, the thermistor resistance will change
enough to permit you to clear the error. Press the
STOP/Reset key to clear the error.
Input
Function Name
State
Sensor When a thermistor is connected to terminals [6]
Open
SJ200 Inverter
Description
and [L], the inverter checks for over-temperature
and will cause trip (E35) and turn OFF the
output to the motor
An open circuit in the thermistor causes a trip,
and the inverter turns OFF the output
Example (requires input configuration—
see page 3–41):
TH
L
6
5
4
thermistor
MOTOR
4–25
3
2
1
PCS