Holding Registers for "A" Group Standard Functions
Func.
Name
Code
A141
A input select for calcu-
late function
A142
B input select for calcu-
late function
A143
Calculation symbol
A145
ADD frequency
A146
ADD direction select
Note 1:
When the value is 10000 (100.0 seconds), a value in the second decimal place
is ignored (for A092/A292 and A093/A293).
R/W
Description
R/W Five options:
00... Digital operator
01... Keypad potentiometer
02... [O] input
03... [OI] input
04... Network variable
R/W Five options:
00... Digital operator
01... Keypad potentiometer
02... [O] input
03... [OI] input
04... Network variable
R/W Calculates a value based on the
A input source (A141 selects)
and the B input source (A142
selects). Three options:
00... ADD (A input + B input)
01... SUB (A input – B input)
02... MUL (A input x B input)
R/W An offset value that is applied
to the output frequency when
the [ADD] terminal is ON.
Range is 0.0 to 400.0 Hz
R/W Two options:
00... Plus (adds A145 value to
the output frequency setting)
01... Minus (subtracts A145
value from the output
frequency setting)
B–31
SJ200 Inverter
Network Data
Reg.
Range
Res.
00E3h
0 to 4
00E4h
0 to 4
00E5h
0 1, 2
00E6h
0 to 4000
0.1 Hz
00E7h
0, 1