Chapter 2

2.11 Control circuit wiring section

Input terminals

• All COMs have the same electric potential.
• Change SW5 to external power source (EX) to connect
the power source between Input terminals 1 to 9, A or
B, and COM.
• Sink or source logic of the input terminal is switched by
SW6.

(Wiring example)

B
A
[USP]
[EXT]
[FW]
• [] it means factory default settings.
Terminal
label
9, 8,
7, 6,
5, 4,
3, 2,
1
A
B
COM
Terminal's default function ([symbol: setting No.])
[RS:028]Reset
• Reset at every trip.
[SCHG:015]Command source change
• Change to the main speed command [AA101](OFF) or
sub-speed command[AA102](ON).
[JG:029]Jogging
• Run at a frequency of [AG-20] upon receipt of the operation
command by [JG]ON.
[FRS:032]Free-run stop
• [FRS]ON sets the motor in a free-run state.
[2CH:031]Two-step acceleration/deceleration
• [2CH]ON enables acceleration/deceleration
time-2[AC124][AC126].
[EXT:033]External trip
• [EXT]ON issues Trip[Er012].
Input terminal
9
8
7
COM
[RV]
[CF2]
Terminal
name
Terminal functions are selectable according to the
Input
parameter settings for each terminal.
terminal
Switching SW6 to SRC or SINK allows you to select SINK or
Source logic.
This is a terminal for pulse input. A and B terminals can be
Pulse input-A
used also as an input terminal.
Terminal functions are selectable according to the
parameter settings for each terminal.
Pulse input-B
The maximum input pulse rate is 32kpps.
This is a common terminal for digital input terminals
Input
(1,2,3,4,5,6,7,8,9,A and B). Three COM terminals are
(common)
available.
Control circuit terminal
SW5
6
5
4
COM
[CF1]
[2CH]
[FRS]
Description
[FW:001]Forward rotation and [RV:002]Reverse rotation
Forward
Reverse
OFF
OFF
ON
OFF
OFF
ON
ON
ON
[CF1:003]Multispeed-1 and [CF2:004]Multispeed-2 commands
Multispeed-1
Multispee
CF1
d-2 CF2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
*) Setting CF3 and 4 allows you to set up to 16-speed.
[USP:034]Unattended start protection
• In a [USP]ON state, if an operation command has been input
before the power supply is ON, Trip[Er013] is issued.
2-19
Installation and Wiring
SW6
3
1
2
COM
[JG]
[RS]
[SCHG]
Electric characteristics
Voltage between each input and
COM terminals
• ON voltage Min.DC18V
• OFF voltage Max.DC3V
• Max. allowable voltage DC27V
• Load current 5.6mA(at DC27V)
Voltage between an input and
COM terminals
• ON voltage Min.DC18V
• OFF voltage Max.DC3V
• Max. allowable voltage DC27V
• Load current 5.6mA(at DC27V)
• Max input pulse rate 32kpps
Description
No command
Forward rotation command operation
Reverse rotation command operation
No command (inconsistent logic)
Description
The set frequency source is enabled.
The frequency source of [Ab-11] is enabled.
The frequency source of [Ab-12] is enabled.
The frequency source of [Ab-13] is enabled.