Hitachi SJ200 Series Instruction Manual page 238

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for SJ200 Series:
Table of Contents

Advertisement

B–24
ModBus Data Listing
The table below lists the holding registers for the "F" Group Main Profile Parameters.
Func.
Code
F001
Output frequency
setting
F002
Acceleration (1) time
(high)
setting *1
F002
(low)
F202
Acceleration (1) time
(high)
setting, 2nd motor *1
F202
(low)
F003
Deceleration (1) time
(high)
setting *1
F003
(low)
F203
Deceleration (1) time
(high)
setting, 2nd motor *1
F203
(low)
F004
Keypad Run key routing R/W Two options; select codes:
Note 1:
Holding Registers, "F" Group Main Profile Parameters
Name
R/W
R/W Standard default target
frequency that determines
constant motor speed,
range is 0.0 / start frequency
to 400 Hz
R/W Standard default acceleration,
range is 0.01 to 3000 sec.
R/W
R/W Standard default acceleration,
2nd motor,
range is 0.01 to 3000 sec.
R/W
R/W Standard default deceleration,
range is
0.01 to 3000 sec.
R/W
R/W Standard default deceleration,
2nd motor,
range is 0.01 to 3000 sec.
R/W
00... Forward
01... Reverse
When the value is 10000 (100.0 seconds), a value in the second decimal place
is ignored.
Description
Reg.
0023h
0024h
0025h
0026h
0027h
0028h
0029h
002Ah
002Bh
002Ch
Network Data
Range
Res.
0 / (start
0.1 Hz
freq. x 10)
to 4000
1 to
0.01
300000
sec
1 to
0.01
300000
sec
1 to
0.01
300000
sec
1 to
0.01
300000
sec
0, 1

Advertisement

Table of Contents
loading

Table of Contents