Using Intelligent Input Terminals - Hitachi SJ100 Series Instruction Manual

Hide thumbs Also See for SJ100 Series:
Table of Contents

Advertisement

4–6

Using Intelligent Input Terminals

Using Intelligent Input Terminals
Terminals 1, 2, 3, 4, 5, and 6 are identical,
programmable inputs for general use. The
input circuits can use the inverter's internal
(isolated) +24V field supply (P24) to power
the inputs. The input circuits are internally
connected to the power supply ground. As the
diagram shows, you can use a switch (or
jumper) to activate an input terminal which
has been programmed. If you use an external
supply, its GND terminal must connect to the
"L" terminal on the inverter to complete the
input circuit. We recommend using the top
row "L" logic GND for login input circuits
and the "L" GND on the bottom row of termi-
nals for analog I/O circuits.
Forward Run/Stop and Reverse Run/Stop Commands:
When you input the Run command via the terminal [FW], the inverter executes the
Forward Run command (high) or Stop command (low). When you input the Run
command via the terminal [RV], the inverter executes the Reverse Run command (high)
or Stop command (low).
Option
Terminal
Code
Symbol
00
FW
01
RV
Valid for inputs:
Required settings:
Notes:
When the Forward Run and Reverse Run
commands are active at the same time, the inverter
enters the Stop Mode.
When a terminal associated with either [FW] or
[RV] function is configured for normally closed,
the motor starts rotation when that terminal is
disconnected or otherwise has no input voltage.
WARNING: If the power is turned on and the Run command is already active, the motor
starts rotation and is dangerous! Before turning power on, confirm that the Run
command is not active.
Function Name
State
Forward Run/Stop
ON
OFF
Reverse Run/Stop
ON
OFF
C01, C02, C03, C04, C05, C06
A02 = 01
Inverter
Input circuits
L
6
5
4
Description
Inverter is in Run Mode, motor runs forward
Inverter is in Stop Mode, motor stops
Inverter is in Run Mode, motor runs reverse
Inverter is in Stop Mode, motor stops
Example:
L
6
5
4
3
See I/O specs on page 4–5.
24VDC
+
P24
3
2
1
RV FW
P24
2
1