"A" Group: Standard Functions

Control Source Settings

The inverter provides flexibility in how you control Run/Stop operation and set the
output frequency (motor speed). It has other control sources that can override the A001/
A002 settings. Parameter A001 sets the source selection for the inverter's output
frequency. Parameter A002 selects the Run command source (for FW or RV Run
commands). The default settings use the input terminals for –FEF (European) models,
and the keypad for –FU (USA) models.
Func.
Name /
Code
SRW Display
A001 Frequency source
setting
F-COM
A002 Run command source
setting
OPE-Mode
Frequency Source Setting - For parameter A001, the following table provides a further
description of each option, and a reference to other page(s) for more information.
Code
00
Keypad potentiometer - The range of rotation of the knob
matches the range defined by B082 (Start frequency adjust-
ment) to A004 (Maximum frequency setting)
01
Control terminal - The active analog input signal on analog
terminals [O] or [OI] sets the output frequency
02
Function F001 setting - The value in F001 is a constant, used
for the output frequency
03
ModBus network input - The network has a dedicated
register for inverter output frequency
10
Calculate function output - The Calculate function has user-
selectable analog input sources (A and B). The output can be
the sum, difference, or product (+, –, x) of the two outputs.
"A" Function
Description
Five options; select codes:
00... Keypad potentiometer
01... Control terminal
VR
02... Function F001 setting
03... ModBus network input
10... Calculate function output
Three options; select codes:
01... Control terminal
02... Run key on keypad, or
REM
digital operator
03... ModBus network input
Frequency Source
SJ200 Inverter
Defaults
Run
Mode
–FEF
–FU
Edit
(EU)
(USA)
01
00
01
02
Refer to page(s)...
2–25
4–51
3–13
,
3–8
B–19
3–28
3–9
Units
3–51
,