14

Gas pressure point

18 The pressure point is closed with a captive screw. Turn screw 6 revolu-
tions anticlockwise to open the pressure point as indicated on figure
23 (a) and place manometer tube over the test point as per figure 23
(b).
23
19. Switch the top two control buttons to "Full On" position as indicated in
figure 24(a) and using a ring spanner, as per figure 24(b), adjust the
pressure to 0.75 kPa for Natural gas or 2.65 kPa for LPG. (Turn clock-
wise to increase pressure and anticlockwise to decrease pressure).
24
20. Switch the heat button back to "Low Flame' position as indicated in
figure 25(a), retain spanner in position and using a screwdriver as
per figure 25(b) adjust the central screw control to give a pressure
reading of 0.3 kPa for Natural Gas and 1.1 kPa for LPG. (Turn clock-
wise to increase pressure and anticlockwise to decrease pressure).
25
21. Switch burners off and remove the manometer tube. Tighten pressure
test point by turning the captive screw fully clockwise.
Replace plastic cap. Ensure the little lug is positioned towards lower
right hand side to clear the control.
22. Refit the lower front cover, making sure not to damage the power cord.