Opto-Isolated Outputs - Baldor 15H SERIES 15H Installation & Operating Manual

15h series inverter control adjustable speed drive
Table of Contents

Advertisement

Section 1
General Information
Figure 3-38 Opto-Input Connections (Using External Supply)
*
User VCC (-)
*
User VCC (+)
Opto Inputs Closing to Ground

Opto-Isolated Outputs

24Com
Optional
Customer
Supplied
Relays &
Diodes
Using Internal Supply
(Sinking the Relay Current)
-
Optional Customer Supplied
10VDC to 30VDC Source
+
Optional
Customer
Supplied
Relays &
Diodes
Using External Supply
(Sinking the Relay Current)
MN715
J4
Opto In #1
Opto In #2
Opto In #3
Opto In #4
Opto In #5
Opto In #6
Opto In #7
Opto In #8
Opto In #9
*
User VCC = 10 - 30VDC External Power Source
Two programmable opto isolated outputs are available at terminals J4-19 through J4-22.
See Figure 3-39. Each output may be programmed to represent one output condition.
The output conditions are defined in Section 4 of this manual.
The opto isolated outputs may be configured for sinking or sourcing 60 mA each, as
shown in Figure 3-39. However, both must be configured the same. The maximum
voltage from opto output to common when active is 1.0 VDC (TTL compatible). The
equivalent circuit for the opto isolated outputs is shown in Figure 3-40.
If the opto outputs are used to directly drive a relay, a flyback diode rated at 1A, 100 V
(IN4002 or equivalent) minimum should be connected across the relay coil.
Each opto output is programmed in the Output programming block.
Figure 3-39 Opto-isolated Output Configurations
+24VDC
Optional Customer Supplied
See recommended terminal tightening torques in Section 6.
Opto In #1
Opto In #2
Opto In #3
Opto In #4
Opto In #5
Opto In #6
Opto In #7
Opto In #8
Opto In #9
*
User VCC (+)
*
User VCC (-)
Opto Inputs Closing to +VCC
24Com
Using Internal Supply
(Sourcing the Relay Current)
-
10VDC to 30VDC Source
+
Using External Supply
(Sourcing the Relay Current)
J4
See recommended terminal
tightening torques in Section 6.
+24VDC
Optional
Customer
Supplied
Relays &
Diodes
Optional
Customer
Supplied
Relays &
Diodes
Receiving & Installation 3-37