Control Installation

Through the Wall Mounting

Keypad Installation

3-2 Receiving & Installation
The control must be securely fastened to the mounting surface at the mounting holes.
Shock Mounting
If the control will be subjected to levels of shock greater than 1G or vibration greater than
0.5G at 10 to 60Hz, the control should be shock mounted.
Control sizes A, B, B2, C2, D2, E and F are designed for panel or through the wall
installation. To mount a control through the wall, a Through the Wall mounting kit must be
purchased (except for B2, C2 and D2 sizes). These kits are:
Kit No.
Description
KT0000A00
Size A control through the wall mounting kit.
KT0001A00
Size B control through the wall mounting kit.
V0083991
Size E control through the wall mounting kit.
V0084001
Size F control through the wall mounting kit.
Refer to Section 6 of this manual for drawings and dimensions of the through the wall
mounting kits.
Procedure:
1.
Refer to the Remote Keypad Installation procedure and mount the keypad.
2.
Connect the keypad cable to the keypad connector of the main control board.