Section 1
General Information
Reset Parameters to Factory Settings
Action
Apply Power
Keypad Display shows this
opening message.
If no faults and programmed for
LOCAL operation.
Press PROG key
Enter program mode.
Press Y or B key
Scroll to Level 2 Blocks.
Press ENTER key
Select Level 2 Blocks.
Press Y or B key
Scroll to the Miscellaneous block.
Press ENTER key
Select Miscellaneous block.
Press Y key
Scroll to Factory Settings
parameter.
Press ENTER key
Access Factory Settings
parameter.
Press Y key
Scroll to STD SETTINGS, to
choose original factory settings.
Press ENTER key
Restores factory settings.
Press Y key
Scroll to menu exit.
Press ENTER key
Return to Miscellaneous block.
Press DISP key
Return to display mode.
MN715
Sometimes it is necessary to restore the parameter values to the factory settings. Follow
this procedure to do so.
Note: All parameter values already programmed will be changed when resetting the
control to factory settings.
Description
Display
Logo display for 5 seconds.
Display mode. Stop LED on.
V
represents blinking cursor.
For 50Hz motors, set to
50Hz/400 VOLTS.
"Loading Presets" is first message
"Operation Done" is next
"No" is displayed last.
Display mode. Stop LED on.
Programming & Operation 4-5
Comments