1-24 RAID Array 3000 Controller Shelf Hardware User's Guide
Power required
Temperature— optimal,
Temperature— minimum required
Relative humidity – optimal
Relative humidity – minimum required
Altitude
Inlet air volume
Air quality
Temperature
Relative humidity
Altitude
Physical characteristics*
*Disk SBBs are not included.
Controller Shelf Power and Physical Specifications
Operating Environment
Table 1-7
110-120/220-240 VAC, 50/60 Hz, single phase,
two 180 Watt power modules @ 2.5 / 1.2 A each
65° F to 75° F (18° C to 24° C)
50° F to 104° F) (10° C to 40° C)
40% to 60% non condensing
10% to 90% non condensing
Maximum wet bulb temperature 82
Minimum dew point: 36
Up to 8,000 ft (2,400 m)
0.026 cubic meter per second
(50 cubic feet per minute)
Not to exceed 500,000 particles per cubic foot of air
at a size of 0.5 micron or larger
-40° F to 151° F (-40° C to +66° C)
8% to 95% non condensing in original shipping
container
From – 300 m to 3,600 m (-1,000 ft. to 12,000 ft )
Installed dimensions
Controller and disk
shelves
Specification
o
o
F (28
C)
o
o
F (2
C)
UPS
continued
Need help?
Do you have a question about the StorageWorks RAID Array 3000 Controller Shelf and is the answer not in the manual?
Questions and answers