Outdoor Installation - Takagi Mobius Water Heater T-M32 ASME Installation Manual And Owner's Manual

On-demand water heater
Hide thumbs Also See for Mobius Water Heater T-M32 ASME:
Table of Contents

Advertisement

1. Follow all local codes, or in the absence of local codes, follow the most recent edition of
the National Fuel Gas Code: ANSI Z223.1/NFPA 54 in the USA or CAN/CSA B149.1
Natural Gas, Propane Installation Code in Canada.
2. Install outdoors only in areas with mild, temperate climates.
3. Ensure that the unit is set for outdoor installation. Locate the left bank of dipswitches to
the bottom of the 7-Seg. LED on the computer board. The 'OUT' dipswitch on that
bank should be switched to its 'ON' (right) position (Do not adjust the right bank of
dipswitches).
Make sure power to the unit is
turned OFF before changing
the dipswitch settings.
7-Seg LED
Left bank of
dipswitches
Right bank of
dipswitches
4. The outdoor vent cap must be used when unit is installed outdoor. Takagi requires the
use of its part No. TM-VC32.
5. When installed outdoors, the T-M32 water heater shall be wall-mounted or mounted on a
stand. Locate the water heater in an open, unroofed area and maintain the following
minimum clearances:
There is a 2" clearance from
the left and right sides of the
unit to combustible and non-
combustible
surfaces. However, if any
portion or area of the surface
is exposed to the exhaust
fumes (i.e. directly to the sides
of the vent cap), that surface
must be at least 24" away.
Keep the clearances.

OUTDOOR INSTALLATION

Front 24"
- 7 -
The dark square is the direction
the dipswitch should be set to.
*
Side 24"
Side 2"
Bottom 12"
O N
TMP1
TMP2
TMP3
MODE
DIRE
OUT
D-PRT
MST
Left Bank of Dipswitches
Top 36"
*
Side 24"
Back 1"
Side 2"
1
2
3
4
5
6
7
8