APPLICATIONS

Toxic chemicals used in boiler treatments such as alcohol, glycerol and glycol group
must not be introduced into the system when used for open loop potable water and
space heating.
The T-M32 can be used to supply potable water and space heating and shall not be
connected to any heating system or component(s) previously used with non-potable
water where any chemicals were added to the water heating appliances.
When the system requires water for space heating at temperatures higher than required
for other uses, a means such as a mixing valve shall be installed to temper the water for
those other uses in order to reduce scald hazard potential.
Water temperature over 125 °F can cause severe burns instantly or death from scalds.
Chemicals such as diluted Glycol can be used for radiant floor, Hydro/fan coil air or
Baseboard heating only. The diluted solution of glycol must contain between 25% and
55% of Glycol. Be aware that in closed-loop glycol systems, low pressure in the heat
exchanger can cause low-temperature boiling, resulting in excessive noise and damage
to the water heater. Consult with the glycol maker for specifications prior to use.

Re-circulation:

* Size the pump to provide at about 2 GPM through the
system at 15 Ft of Head plus applications and piping head
losses. 2 GPM will allow the system to operate at its
optimal performance.
* If the application requires a higher re-circulating flow rate,
make sure that the re-circulating flow rate is no greater
than 4 GPM. If the flow rate is too high, the system could
be damaged by erosion.
Space Heating Applications
WARNING
This is a concept drawing only.
- 42 -