13. Connect the cable from the negative post of the battery to the negative
14. Install the lock washer and nut that are supplied. Tighten the nut to a
15. Slip the DC terminal covers over the XM Series Inverter DC terminals.
16. Use the disconnect/battery selector switch to select one of the batteries

Testing Your Installation

There are two tests to be performed. The first test verifies that the XM Series
Inverter is inverting DC power from the batteries to provide AC power to
operate AC devices.
The second test is intended for installations where AC input and output is
hardwired to the XM Series Inverter. The test verifies that the XM Series
Inverter transfers from inverter power to shore power when shore power is
present.
Note:
grid, generator or external AC source.
When you are ready to test your installation and operate the XM Series
Inverter, close the DC fuse and Disconnect or the DC circuit breaker to
supply DC power to the XM Series Inverter.
975-0263-01-01
WARNING: Explosion or fire
Do not complete the next step if flammable fumes are present. Explosion or fire
may result if the disconnect/battery selector switch is not in the off position.
Thoroughly ventilate the battery compartment before making this connection.
DC terminal of the inverter.
torque of 108–120 in-lbf (12.2–13.6 N-m). Make the connection snug
enough so the ring terminal does not move around on the DC terminal,
but do not overtighten.
or battery banks (the house bank is preferred over the start bank).
WARNING: Shock hazard
The on/off button on the XM Series Inverter remote panel does not disconnect
DC or AC input power to the XM Series Inverter.
Shore power (pass-through) refers to the AC input power from a utility
Testing Your Installation
3–21