Installation
AC output
ground screw
AC knockout
Figure 3-5 XM Series Inverter AC Wiring Compartment
3–16
ST ATUS
Utili t y
Battery
Fault
GND
AC
OUT
CAUTION!
source ofpower. Damageto unit may occur.
8. Strip about 2 inches (50 mm) from the jacket of the AC input cable.
The AC input cable may be either solid or stranded, but must have
three conductors and be sized as in Table 3-3 on page 3–14. (The AC
terminal block accepts wire sizes up to No. 10 AWG.)
9. Strip approximately 3/8 inch (10 mm) off the insulation of each
conductor.
10. Run the AC cable through the right-hand side strain-relief clamp and
into the wiring compartment.
11. Fasten the Ground wire to the grounding screw.
12. Using the 1/8 inch slot screwdriver, loosen the wire attachment
screws on the terminals.
CAUTION: Reverse polarity
Improper connections (connecting a line conductor to a neutral conductor, for
example) will cause the XM Series Inverter to malfunction and may permanently
damage the inverter. Damage caused by a reverse polarity connection is not
covered by your warranty.
13. Insert the Line and Neutral wires into the corresponding terminals.
14. Tighten the wire attachment screws to a torque of 1.3–1.8 lbf-ft
(1.76–2.44 Nm). Leave some wiring slack inside the wiring
compartment.
15. Secure the strain-relief clamp.
16. See "Connecting AC Output to an Existing AC Circuit".
Input Voltage (V)
S elect
Input C urrent (A)
Output P ower (W)
XM1000
GND
AC
N
L
N
L
IN
Do not connect the AC OUT to any other
AC input
ground screw
AC knockout
975-0263-01-01