5.9.2
Hot Water Reheat Coil
Building hot water can be piped to a factory-installed hot water reheat coil, located downstream of the
cooling coil. A factory-installed solenoid valve opens upon a call for reheat.
Figure 25 Optional hot water reheat (two-way valve)
Water
Return
From Unit
Shutoff
Valves *
Hose
Bibs *
Water
Supply
To Unit
Y-Strainer
* Components are not supplied
by Liebert but are recommended
for proper circuit operation and
maintenance.
Bleed Valve
Hot Water
Reheat
Control
Valve
Hot Water
Reheat
Coil
FIELD PIPING
FACTORY PIPING
NOTE: Hot water reheat only available
on chilled water units.
DPN000197
Rev. 2
41
Site Preparation and Installation
®
Liebert