Figure i Model number designation External Telecommunication Nominal Btuhs (1000) 0=Standard Supply & Return 7 = Scroll Compressor Openings with POE oil, R-407C R = Right Compressor L = Left Compressor P = 208/230V – 1 ph - 60 Hz S = 220/240 –...
Space Savings The Liebert InteleCool2 does not use any of the valuable floor space inside the secure space. Instead, it is mounted on the outside wall. No additional space is required outside or on a roof. Easy to Install The Liebert InteleCool2 is assembled, wired, piped, charged with refrigerant and factory tested as a system to ensure trouble-free installation and startup.
Compressor Crankcase Heater An optional compressor crankcase heater is available for use with the scroll compressor, but it is not required because the refrigerant charge of the Liebert InteleCool2 unit with scroll compressor is less than the compressor critical charge.
Refrigeration System Options Low-Pressure Switch and Low-Pressure Bypass Timer Low-Pressure Switch: Used to protect the Liebert InteleCool2 if the evaporator blower fails, the air filter becomes clogged, the refrigeration circuit malfunctions or if there is loss of refrigerant. The low-pressure switch is activated when the suction pressure drops below its cutout setting. When activated, the low-pressure switch inhibits operation of the compressor and condenser fan.
2.1.2 Location Considerations The Liebert InteleCool2 unit is field-mounted on an outside wall. Additional framing in the wall may be required to ensure adequate structural support. The outdoor area near the condenser supply and discharge must also be considered. To ensure adequate air supply, the unit should be mounted in a clean area, away from loose dirt and foreign matter that may clog the condenser coil.
(111) Piping Connections The Liebert InteleCool2 is a self-contained, packaged unit. All refrigerant piping connections are made at the factory, so no external condenser is required. The evaporator coil condensate drain is factory-supplied and drains outdoors through the unit base pan. The condensate drain tubing should be checked to be certain that it is placed through the hole provided in the base pan.
Make sure that the voltage supplied agrees with the voltage specified on the unit nameplate. The Liebert InteleCool2 comes standard with a factory-installed circuit breaker, accessible through an external access panel. An external, wall-mounted power disconnect switch (field-supplied) may be required for local codes.
If you have questions, contact the thermostat manufacturer. Liebert Dual Unit Control The Liebert Dual Unit Control is designed to control two Liebert InteleCool2 units in a “lead/lag” fashion. The control contains an electronic timer for switching the operating sequence of two units on a one-, two-, four-, or eight-day basis.
3. Reconnect 24VAC to terminals TR and TR1 and adjust potentiometer for desired minimum position by turning Q709 adjustment screw clockwise to increase minimum position; counterclockwise to decrease minimum position. Figure 3 Mounting minimum position potentiometer on actuator Push onto actuator ® ® Liebert InteleCool...
Disconnect all local and remote electric power supplies before working within. Potentially lethal voltages exist within this equipment during operation. Observe all cautions and warnings in this manual. Only qualified service and maintenance personnel should work with this equipment. ® ® Liebert InteleCool...
ROCEDURE Verify that installation is complete by using the Checklist for Complete Installation. 1. Disconnect all power to the Liebert InteleCool2 unit. 2. Adjust remote control to prevent compressor, heat and fan operation. 3. Turn on main breaker and check line voltage on main unit disconnect switch. Line voltage must be within ±...
Compressorized cooling is provided by a high-efficiency system consisting of a compressor, thermostatic expansion valve, evaporator, and condenser coil. The Liebert InteleCool2 uses R-407C refrigerant in a conventional vapor-compression refrigeration cycle. Heat is removed from the air in the space by blowing the air across the evaporator coil. As heat is transferred to the refrigerant in the evaporator, the refrigerant boils and turns to a warm vapor.
Heating - Optional On units supplied with optional resistance heating, a call for heating closes the heat relay and energizes the evaporator fan and resistive elements. ® ® Liebert InteleCool...
The high-pressure switch is mounted in the liquid line. Electrically, it is connected in series with the compressor start circuit, which will shut down the compressor and condenser fan if the liquid pressure exceeds 400 PSIG (2758 kPa). This protects the Liebert InteleCool2 in the event of condenser motor failure or condenser coil blockage.
Includes a low-pressure switch, low-pressure bypass timer (described above) and fan cycle control. Fan Cycle Control—Condenser Fan Cycling Control; allows the Liebert InteleCool2 unit to provide cooling to the space when the outdoor ambient temperature is lower than 50°F (10°C) and down to -20°F (-28.9°C).
Each month, the components of the refrigeration system should be inspected for proper function and signs of wear. Since, in most cases, evidence of malfunction is present prior to component failure, periodic inspections can be a major factor in the prevention of most system failures. ® ® Liebert InteleCool...
The correct superheat setting is between 10° and 20°F (5.5° and 11.1°C) under normal load conditions and “steady-state” operation. Some models of the Liebert InteleCool2 will be supplied with a non-adjustable expansion valve, so no adjustments are possible.
Page 23
Alco Dri-Kleener. Whichever kit is used, follow the manufacturer’s procedure. CAUTION Risk of caustic material. Can cause personal injury. Avoid skin contact with the refrigerant and oils. Severe burns will result. Use long rubber gloves when handling contaminated parts. ® ® Liebert InteleCool...
High-side gauge port is a liquid line connection. Proper procedures should be followed when installing and removing gauges. A 6-foot (1.8 m) hose can hold up to 3 oz (0.1 l) of refrigerant. Be sure to purge high side to low prior to removal. ® ® Liebert InteleCool...
36" (914mm) when mounted adjacent to another unit, for component access. For recommended minimum clearances, refer to 2.1.2 - Location Con- siderations. 2-1/4" (58mm) See Table 5 below for dimensions. Table 5 Liebert InteleCool2 dimensions, in. (mm) Dimensions, in. (mm) Model 37-1/8 17-3/4 38-3/4 9-3/8 9-13/32...
Weight w/ Economizer Ib (kg) 350 (159) 350 (159) * Based on rated airflow at 0.2 IN WG (50 Pa) external static and no outside air. ** For applications above 110°F (43°C) use high ambient option. ® ® Liebert InteleCool...
Weight - with Economizer, Ib (kg) 490 (222) 490 (222) * Based on rated airflow at 0.2 IN WG (50 Pa) external static and no outside air. ** For applications above 110°F (43°C) use high ambient option. ® ® Liebert InteleCool...
150 (330) Weight - with Economizer, kg (Ib) 159 (350) * Based on rated airflow at 50 Pa (0.2 IN WG) external static and no outside air. ** For applications above 43°C (110°F) use high ambient option. ® ® Liebert InteleCool...
Weight - with Economizer, kg (lb) 222 (490) 222 (490) * Based on rated airflow at 50 Pa (0.2 IN WG) external static and no outside air. ** For applications above 43°C (110°F) use high ambient option. ® ® Liebert InteleCool...
Drain Connection - ID, in. Weight w/o Economizer, Ib (kg) 330 (150) 330 (150) Weight w/ Economizer, Ib (kg) 350 (159) 350 (159) * Based on rated airflow at 0.2 IN WG (50 Pa) external static and no outside air. ® ® Liebert InteleCool...
Drain Connection - ID, in. Weight - w/o Economizer, Ib/kg 470 (213) 470 (213) Weight - with Economizer, Ib/kg 490 (222) 490 (222) * Based on rated airflow at 0.2 IN WG (50 Pa) external static and no outside air. ® ® Liebert InteleCool...
Drain Connection - ID, in. 3/4 (1.9) Weight - w/o Economizer, kg (Ib) 150 (330) Weight - with Economizer, kg (Ib) 159 (350) * Based on rated airflow at 50 Pa (0.2 IN WG) external static and no outside air. ® ® Liebert InteleCool...
Weight - with Economizer ,kg (lb) 222 (490) 222 (490) * Based on rated airflow at 50 Pa (0.2 IN WG) external static and no outside air. ** For applications above 43°C (110°F) use high ambient option. ® ® Liebert InteleCool...
No voltage output Check stat for proper output to W terminal. from thermostat Heat does not operate Fusible link blown Check for open and replace. Bad contactor Check for open and replace. ® ® Liebert InteleCool...
Page 60
+39 049 9719 111 Fax: +39 049 5841 257 While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no Asia responsibility and disclaims all liability for damages resulting from use of 29/F, The Orient Square Building this information or for any errors or omissions.