Page 5
Motor parts, heater, Economizer, 1.5- and 2-ton units ....... . .
Page 6
Figure i Model number designation External Telecommunication 0=Standard Supply & Return Openings 3=4 or 5 Ton Unit With 3 Ton Supply & Return Openings 0 = Standard F = Fixed Outside Air Damper E = Economizer Nominal Btuhs (1000) H = Hermetic Compressor S = Scroll Compressor R = Right Compressor L = Left Compressor...
Evaporator air is supplied by a direct drive blower package. Fans are centrifugal, double width, dou- ble inlet. Filter The filter is 2 inches deep, pleated, with a minimum efficiency rating of 20% (based on ASHRAE stan- dard 52.1). Located within the cabinet, the filter is serviceable from the front of the unit. Cabinet The exterior cabinet is constructed of painted steel.
A normally open set of contacts is provided to terminals 2 and 3 of the customer terminal strip for monitoring the status of the lock out relay when this option is sup- plied without the Common Alarm option.
1-2-4-8 day sequence. Unit lead selector, unit 1 & 2 power-on LEDs, unit 1 or 2 lead unit LEDs, 48 hour program save on loss of power, industry standard connections and 24V power from each unit. The DUC provides auto sequencing and displays on-status and operating- status parameters.
To install the unit, follow the instructions below. 1. Verify that an adequate structural support is provided for the unit. 2. Using a chalk line, mark the outside wall with a level horizontal line, where the bottom of the unit is to rest.
The condensate drain tubing should be checked to be certain that it is placed through the hole provided in the base pan. 11" 11" 11" (279mm) (279mm) (279mm) M ref. InteleCool 2 dimensional data in. (mm) 9-3/8 9-13/32 20-3/4 25-1/16 (238) (239) (203) (527)
(customer supplied or Liebert option). DO NOT RUN CONTROL WIRING WITH HIGH VOLTAGE! 2.5.1 Power Connections All power and control wiring and ground connections must be in accordance with the National Electri- cal Code and local codes Use copper wiring only.
It also contains a two-stage heat/two-stage cool thermostat with individual heat and cool set points. Light emitting diodes (LEDs) indicate Lead Unit 1 or 2 and power from Unit 1 or 2. The schedule for lead/lag switchover is adjustable by moving jumpers on the printed cir- cuit board.
Units supplied with Economizer requiring outside air can be adjusted as follows: 1. Run motor to fully closed position and disconnect 24 VAC from terminals TR and TR1. 2. Connect minimum position potentiometer to terminals P and P1. (See Figure 3. T and T1 are disconnected.) 3.
HECKLIST FOR OMPLETE ___ 1. Proper clearance for service access has been maintained. ___ 2. Equipment is level and mounting fasteners are tight. ___ 3. Ducting completed, if required. ___ 4. Line voltage to power wiring matches equipment nameplate. ___ 5. Power wiring connections completed to disconnect switches, including earth ground. Proper phase rotation has been observed so that scroll compressor will rotate in the correct direction.
Verify that installation is complete by using the Checklist for Complete Installation. 1. Disconnect all power to the InteleCool2 unit. 2. Adjust remote control to prevent compressor, heat and fan operation. 3. Turn on main breaker and check line voltage on main unit disconnect switch. Line voltage must be within ±...
Liquid refrigerant then passes through the thermal expansion valve and into the evap- orator. The expansion reduces the pressure and temperature to complete the cycle. Figure 4 Refrigeration system Compressors: Hermetic Reciprocating (1.5, 2 and 3 ton units) or Scroll Optional compressor location available Evaporator Liquid line...
5.2.1 Enthalpy Sensor The enthalpy sensor responds to the total heat content of the outdoor air to provide changeover from compressorized cooling to free-cooling operation.
Contact closures between the 24 VAC (R) and different control connections supply control voltage to the electric panel components responsible for the desired function. Operating modes are controlled by contact closures as follows: Table 2 Operating modes/contact closures Connection Operating Mode...
A normally open set of contacts is provided to terminals 2 and 3 of the customer terminal strip for monitoring the status of the lock out relay when this option is sup- plied without the Common Alarm option.
6.5.2 Discharge Pressure Discharge pressure can be increased or decreased by load conditions or condenser efficiency. The high-pressure switch will shut the compressor/contactor at its cut-out setting of 400 PSIG (2758 kPa). See 5.4.2 - High Pressure (Standard). Maintenance...
To adjust the superheat setting when an adjustable valve is used: 1. Remove the valve cap from the base of the valve. 2. Turn the adjustment stem counter-clockwise to lower the superheat. 3. Turn the adjustment stem clockwise to increase the superheat.
1. Disconnect power. 2. Attach suction and discharge gauges to access fittings. 3. Recover refrigerant using standard recovery procedures and equipment. Use a filter drier when charging the system with recovered refrigerant.
Evacuate the system twice to 1500 microns, and the third time to 500 microns. Break the vacuum each time with dry nitrogen to 2 PSIG (13.8 kPa). 10. Charge the system with refrigerant. Refer to unit serial tag for refrigerant charge amount.
34" (864mm) in front and 30" (762mm) each side, or 36" (914mm) when mounted adjacent to another unit, for component access. For recommended minimum clearances, refer to 2.1.2 - Location Con- siderations. See Table 5 below for dimensions. Table 5 InteleCool2 dimensional data in.
650 (1100) 710 (1210) 570 (970) 620 (1050) 0.25 (0.19) 0.25 (0.19) 16 x 32.5 x 2 - one 16 x 32.5 x 2 - one (40.6 x 82.5 x 5) (40.6 x 82.5 x 5) 330 (150) 330 (150)
Total 115°F (46.1°C)** Sensible Evaporator Air Flow - Dry Coil (Derate ESP by 0.2 - IN WG (50 Pa) for ET348 and ET360) External Static Pressure 0.0 - IN WG (0.0 Pa) 0.1 - IN WG (25 Pa) 0.2 - IN WG (50 Pa) 0.3 - IN WG (75 Pa)
Evaporator Air Flow - Dry Coil (Derate ESP by 0.15 - IN WG (50 Pa) for ET347 and ET359) External Static Pressure 0.0 Pa (0.0 - IN WG) 25 Pa (0.1 - IN WG) 50 Pa (0.2 - IN WG) 75 Pa (0.3 - IN WG) 100 Pa (0.4 - IN WG) 125 Pa (0.5 - IN WG) Evaporator Air Flow - Wet Coil (Derate ESP by 0.15 - IN WG (50 Pa) for ET347 and ET359)
ROUBLESHOOTING Table 14 Troubleshooting guide Problem Probable Cause Unit will not start No power to unit Control voltage circuit breaker open Shut off by external thermostat or stat is defective No cooling Low refrigerant charge Compressor contactor not pulling in No output from thermostat Unit cycles on...
10.0 P ARTS Table 15 Refrigeration system parts, 1.5 and 2 ton units Figure Part Name/ Description Run capacitor, recip comp Cap. 25μF, 370V Cap. 30μF, 370V Run capacitor, scroll comp Cap. 30μF, 370V Cap. 40μF, 370V Compressors, reciprocating Comp. 220/240-1 Comp.
Table 23 Motor parts, heater, Economizer, 1.5- and 2-ton units Figure Part Name/ Description Condenser fan motors Standard Motor 1/8 Hp, 208/230V (std) Motor 1/8 Hp, 380/460V (std) Fan prop, 2 blade, 20", 28-deg High ambient option 1/5 Hp, 208/230V (high amb) 1/5 Hp, 380/460V (high amb) Fan prop, 4 blade, 20", 22-deg...
Min position potentiometer 13-3 Enthalpy control 13-4 Mixed air sensor 13-5 Push rod 13-6 Linkage, ball type 13-7 Filter, 20%, 2" x 21" x 36.25" ET047N ET047M ET347N ET347M 200-230V 380-415V Part # 3 Ph 50 Hz 3 Ph 50 Hz...
Min position potentiometer 13-3 Enthalpy control 13-4 Mixed air sensor 13-5 Push rod 13-6 Linkage, ball type 13-7 Filter, 20%, 2" x 21" x 36.25" ET059N ET059M ET359N ET359M 200-230V 380-415V Part # 3 Ph 50 Hz 3 Ph 50 Hz...
Need help?
Do you have a question about the InteleCool 2 and is the answer not in the manual?
Questions and answers