Specifying An Operation Mode, Using Parameters - Toshiba TOSVERT VF-S11 Instruction Manual

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

5.3

Specifying an operation mode, using parameters

• Function
Automatically programs all parameters (parameters described below) related to the functions by selecting
the inverter's operating method.
The major functions can be programmed simply.
[Parameter setting]
Title
Note: When this parameter is invoked after it has been set, 0 is always displayed (on the right side).
5
The number on the left side refers to the number specified previously.
Example
Automatically programmed functions and parameter set values
Relational
parameter
(Always)
(F)
(R)
(RES)
(S1)
(S2)
(S3)
Note) See K-16 for input terminal functions.
Disabled (
The parameter does nothing. Even if set to 0, au4 will not return the setting you made to its factory
default.
: Parameter setting macro function
Function
Parameter setting macro function
Default setting
1: Coast stop
value
1: Operation
0: Terminal board
panel
0: Potentiometer
0: Potentiometer
1: ST
0: Disabled
2:F
2:F
3:R
3:
10: RES
10: RES
6: SS1
6: SS1
7: SS2
7: SS2
8: SS3
1: ST
0 (%)
-
= )
Adjustment range
0: Disabled
1: Coast stop
2: 3-wire operation
3: External input UP/DOWN setting
4: 4-20mA current input operation
2: 3-wire
3: External input
operation
UP/DOWN
setting
0: Terminal board
0: Terminal board
5: UP/DOWN
from external
0: Potentiometer
contact
1: ST
1: ST
2:F
2:F
3:R
3:R
10: RES
10: RES
6: SS1
41:UP
7: SS2
42: DOWN
49: HD
43: CLR
-
-
E-6
E6581158
Default setting
0:
4: 4-20mA
current input
operation
0: Terminal board
1: VIA
1: ST
2:F
3:R
10: RES
6: SS1
7: SS2
38: FCHG
20 (%)