• Function
Parameter setting
6
*
Note: When using the VIA terminal as a contact input terminal, be sure to turn the VIA slide switch to the V
✩ The figure on the right shows an example of the connection of input terminals VIA and VIB when they are
used as contact input terminals. This example illustrates the connection when the inverter is used in sink
logic mode.
✩ The figure on the right shows an example of the
connection of input terminals VIA and VIB when they
are used as contact input terminals. This example
illustrates the connection when the inverter is used in
sink (Negative) logic mode.
Changing the functions of VIA and VIB terminals
: VIA/VIB terminal function selection
This parameter allows you to choose between signal input and contact signal input for the VIA and VIB
terminals.
Title
Function
Analog/contact input
function selection
(VIA/VIB terminal)
When using the VIA and VIB terminals as contact input terminals in sink logic connection, be sure to
insert a resistor between the P24 terminal and the VIA/VIB terminals. (Recommended resistance: 4.7kΩ-
1/2W)
position.
Adjustment range
0: VIA - analog input
VIB - anolog input
1: VIA - anolog input
VIB - contact input (Sink)
2: VIA - analog input
VIB - contact input (Source)
3: VIA - contact input (Sink)
VIB - contact input (Sink)
4: VIA - contact input (Source)
VIB - contact input (Source)
4.7kΩ
F-6
E6581158
Default setting
0
P24
VIA
V
I
VIA(VIB)
CC