Toshiba TOSVERT VF-S11 Instruction Manual page 161

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

Title
Detection of output short-circuit during
start-up
6.19.9 Over-torque trip
: Over-torque trip/alarm selection
: Over-torque detection level
: Over-torque detection time
: Over-torque detection level hysteresis
• Function
Use the
parameter to trip the inverter or to output the alarm if a torque currrent exceeding the
-specified level flows for more than the
as "
".
= : .......... No tripping (FL relay deactivated).
An over-torque alarm can be put out by setting the output terminal function selection
parameter.
= : .......... The inverter is tripped (FL relay activated) only after a torque current exceeding the
Title
Over-torque trip/alarm selection
Over-torque detection level
Over-torque detection time
Over-torque detection level hysteresis
Function
0: Each time (standard pulse)
1: Only one time after power is
2: Each time (short-time pulse)
3: Only one time after power is
-specified level has been detected for more than the
Function
0: Alarm only
1: Tripping
0-250 (%)
0.0-10.0 [sec]
0-100 (%)
F-67
Adjustment range
turned on (standard pulse)
turned on (short-time pulse)
-specified time. Trip information is displayed
Adjustment range
E6581158
Default setting
0
6
-specified time.
Default setting
0
150
0.5
10