6. Extended parameters
Extended parameters are provided for sophisticated operation, fine adjustment and other special purposes. Modify
parameter settings as required. See Section 11, Table of extended parameters.
6.1
Input/output parameters
6.1.1
Low-speed signal
• Function
When the output frequency exceeds the setting of
can be used as an electromagnetic brake excitation/release signal.
This signal can also be used as an operation signal when
signal is put out if the output frequency exceeds 0.0Hz.
Relay output (250Vac-1A (cosφ=1), 30Vdc-0.5A, 250Vac-0.5A (cosφ=0.4)
at RY-RC, FLA-FLC-FLB terminals (Default setting: RY-RC).
If the inverter is so set, the signal will be put out through the open collector OUT and NO output
terminals (24 Vdc-Max. 50 mA).
[Parameter setting]
Title
: Low-speed signal output frequency
Function
Low-speed signal output frequency
Output frequency
[Hz]
Set frequency
Low-speed signal output
RY-RC terminals (Default setting)
P24-OUT terminals
FLA-FLC-FLB terminals
Low-speed signal output:
Inverted
an ON signal will be generated. This signal
is set to 0.0Hz, because an ON
Adjustment range
0.0 ∼
(Hz)
0
F-1
E6581158
6
Default setting
0.0
Time [s]
ON
OFF
ON
OFF