Toshiba TOSVERT VF-S11 Instruction Manual page 41

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

Terminal
Input/output
symbol
Common to
Control circuit's equipotential terminal (3
CC
Input/output
terminals)
PP
Output
Analog power supply output
Multifunction programmable analog input.
Factory default setting: 0~10Vdc and
0~60Hz (0~50Hz) frequency input.
The function can be changed to
4~20mAdc (0~20mA) current input by
flipping the dip switch to the I position.
VIA
Input
By changing parameter setting, this
terminal can also be used as a
multifunction programmable contact input
terminal. When using the sink logic, be
sure to insert a resistor between P24-VIA
(4.7 kΩ-1/2 W). Also move the VIA dip
switch to the V position.
Multifunction programmable analog input.
Standard default setting: 0~10Vdc input
and 0~60Hz (0~50Hz) frequency
By changing parameter setting, this
VIB
Input
terminal can also be used as a
multifunction programmable contact input
terminal. When using the sink logic, be
sure to insert a resistor between P24 and
VIB. (4.7 kΩ-1/2 W)
Multifunction programmable analog
output. Standard default setting: output
frequency.
FM
Output
The function can be changed to 0-20mAdc
(4-20mA) current output by flipping the FM
slide switch to the I position.
Function
(internal impedance:
impedance: 30kΩ)
1mAdc full-scale
ammeter or 7.5Vdc
(10Vdc)1mA full-
scale voltmeter
0-20mA (4-20mA)
DC ammeter
Permissible load
resistance:
750Ω or less
B-7
Electrical
Inverter internal circuits
specifications
CC
10Vdc
PP
(permissible load
current: 10mA)
0.47
10Vdc
VIA
30kΩ)
VIA
4-20mA
(internal impedance:
250Ω)
10Vdc
VIB
(internal
FM
FM
E6581158
+24V
2
Voltage
conversion
+5V
15k
300
V
15k
I
250
+5V
15k
15k
4.7K
+
-
P24
V
I
+
-
100

Advertisement

Table of Contents
loading