Toshiba TOSVERT VF-S11 Instruction Manual page 176

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

* Disabled............ Indicates that the inverter will not be tripped even if a communication error occurs.
Trip .................. The inverter trips when a communication time-over occurs.
6.22.2 Using the RS232C/RS485
Setting the communication functions
Setting commands and frequencies by communications has priority over sending commands from the
6
operation panel or the terminal board. Command/frequency setting by communications can therefore be
enabled, irrespective of the setting in the command mode (
When inverters are connected to each others, however, in order for slave inverters to recognize frequency
signals from the master inverter as frequency commands, the frequency setting mode selection 1 parameter
(
COMMUNICATIONS EQUIPMENT USER'S MANUAL for details.
However, when the input terminal function selection parameter is set to 48: SC/LC (Serial/Local selection),
the inverter can be operated with the settings of the command mode (
(
Transmission specifications
Transmission scheme
Connection scheme
Synchronization scheme
Transmission rate
Character transmission
Stop bit length
Error detection
Character transmission format
Order of bit transmission
Frame length
Title
Function
Block read data 1
Block read data 2
Block read data 3
Block read data 4
Block read data 5
Free notes
In this case a trip information
) provided for each slave inverter needs to be set to 4 (serial communications). Refer to the
) by external input.
Item
Adjustment range
0: No selection
1: Status information
2: Output frequency
3: Output current
4: Output voltage
5: Alarm information
6: PID feedback value
7: Input terminal board monitor
8: Output terminal board monitor
9: VIA terminal board monitor
10: VIB terminal board monitor
0-65535
flashes on and off on the operation panel.
) or the frequency setting mode (
Specifications
Half-duplex
Centralized control
Asynchronous
Default: 9600 baud (parameter setting)
Option: Either 1200, 2400, 4800, 9600, or 19200baud
ASCII code: JIS X 0201 8, 8-bit (fixed)
Binary code: Binary, 8-bit (fixed)
Inverter receiving: 1 bit, Inverter sending: 2 bits
Parity: Even, Odd, or None selectable by parameter setting;
check sum method
Receiving: 11-bit, Sending: 12-bit
Least significant bit first
Variable to a maximum of 17 bytes
F-82
E6581158
Default setting
0
0
0
0
0
0
) or the frequency setting mode
).