Toshiba TOSVERT VF-S11 Instruction Manual page 226

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

Communication
Title
Function
No.
0609
Small current
detection current
hysteresis
0610
Small current
trip/alarm
selection
0611
Small current
detection current
0612
Small current
detection time
0613
Detection of
output short-circuit
during start-up
0615
Over-torque
trip/alarm
selection
0616
Over-torque
detection level
0618
Over-torque
detection time
0619
Over-torque
detection level
hysteresis
0621
Cumulative
operation time
alarm setting
0626
Over-voltage stall
protection level
0627
Undervoltage
trip/alarm
selection
0633
Trip at VIA low
level input mode
0634
Annual average
ambient
temperature (parts
replacement
alarms)
*1 : Default values vary depending on the capacity. See the table of K-15.
Minimum
setting unit
Unit
Adjustment range
Panel/Commun
ication
%
1/1
1-20
-
-
0: Alarm only
1: Tripping
%
1/1
0-100
(A)
s
1/1
0-255
-
-
0: Each time (standard pulse)
1: At start-up (only one time after
power is turned on)
(standard pulse)
2: Each time (short-time pulse)
3: At start-up (only one time after
power is turned on)
(short-time pulse)
-
-
0: Alarm only
1: Tripping
1/1
0-250
%
s
0.1/0.1
0.0-10.0
%
1/1
0-100
100
0.1/0.1
0.0-999.9
Time
(=10 hours)
1/1
100-150
%
-
-
0: Alarm only
(detection level below 60%)
1: Tripping
(detection level below 60%)
2: Alarm only
(detection level below 50%,
DC reactor necessary)
1/1
0: Disabled, 1-100
-
-
1: -10 to +10°C
2: 11-20°C
3: 21-30°C
4: 31-40°C
5: 41-50°C
6: 51-60°C
K-11
E6581158
Default
User
Reference
setting
setting
10
6.19.7
0
0
0
0
6.19.8
0
6.19.9
150
0.5
10
6.19.9
610
6.19.10
*1
6.13.5
0
6.19.12
0
6.19.13
3
6.19.14
11