Toshiba TOSVERT VF-S11 Instruction Manual page 42

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

Terminal
Input/output
symbol
P24
Output
2
OUT
Output
NO
FLA
FLB
Output
FLC
RY
Output
RC
* PTC (Positive Temperature Coefficient) : Resettable thermal fuse resistor for over current protection
Function
24Vdc power output
Multifunction programmable open collector
output. Standard default settings detect
and output speed reach signal output
frequencies.
Multifunction output terminals to which two
different functions can be assigned.
The NO terminal is an isoelectric output
terminal. It is insulated from the CC
terminal.
By changing parameter settings, these
terminals can also be used as
multifunction programmable pulse train
output terminals.
Multifunction programmable relay contact
output.
Detects the operation of the inverter's
protection function.
Contact across FLA-FLC is closed and FLB-
FLC is opened during protection function
operation.
Multifunction programmable relay contact
output.
Standard default settings detect and
output low-speed signal output
frequencies.
Multifunction output terminals to which two
different functions can be assigned.
Electrical
specifications
24Vdc-100mA
Open collector output
24Vdc-50mA
To output pulse
trains,
a current of 10mA
or more needs to
be passed.
Pulse frequency
range:
38∼1600Hz
250Vac-1A
(cosφ=1)
: at resistance load
30Vdc-0.5A
250Vac-0.5A
(cosφ=0.4)
250Vac-1A
(cosφ=1)
: at resistance load
30Vdc-0.5A
250Vac-0.5A
(cosφ=0.4)
B-8
E6581158
Inverter internal circuits
+24V
P24
PTC
*
*
10
PTC
OUT
10
NO
+24V
FLA
FLB
RY
FLC
+24V
RY
RY
RC